22
2. Restart after instantaneous power failure
This function if different from free run restart, the inverter control power is
maintained above 5V.
Restart after instantaneous
power failure: no function
When it detects low voltage “PLU”, it activates “STOP”,
“PLU”. After recovery of voltage, “PLU” are de-active,
“STOP” remains the same, and it will have to switch
“ON” again to restart if you select external control, if
you select panel control, just press “FWD” or “REW”
key to restart.
Restart after instantaneous
power failure: with function
Restart motor under free run.
15msec.
Power Supply
External Switch
Inverter Power
Motor Speed
Instantaneous power
failure, Voltage loss
Note: The inverter will be de-active when control voltage is less than 5V.
Apply with free run restart function when it is required.
§
Cd29
Time (Settable range 0~9000)
This function must accommodate Cd47=0 setting.
When motor starts operation, the time counter is active.
§
Cd30
Stop by panel key (Settable range 0~1)
Cd30=0 No function
Cd30=1 with function
Stop function: This function enables the inverter to be stopped by panel
key while the inverter is operated by external sequence.