38
§
CE52
Choice of multi-speed record file (settable range 1~6)
The function cannot be modified during revolution
The setting cannot be changed while the machine is working.
According to the needs of the user, choose different file for the current step, the data
CE05~CE36 are stored in the files.
§
CE53
Multi-steps all files set to default (settable range 0~1)
The function cannot be modified during revolution
The setting cannot be changed while the machine is working.
CE53=0 Data remain unchanged.
CE53=1 Reset data in files 1-2 to default.
§
CE54
Multi-steps memory duplicate function (settable range 1~6)
The function cannot be modified during revolution
The setting cannot be changed while the machine is working.
Duplicate current using file (CE05~CE36) to CE54 .
§
CE61
Input terminal for Set Point and PI feedback (settable range 0~5)
The function cannot be modified during revolution
CE61
Target value
PI feedback
terminal
0
Cd00
IN1
1
Cd00
IN2
2
CE67
IN1
3
CE67
IN2
4
IN1
IN2
5
IN2
IN1
Note:
1. IN1(4~20mA) scale to 0~100.0 %
,
IN2
、
IN3(0~10V) scale to 0~100.0 %
2. Make sure this parameter setting does not conflict with the setting for Cd01
(Set frequency source).
Ex: If Cd01=1 then the parameter CE61 cann’t be modify to 1, 3 or 4.
§
CE62
Proportion gain (settable range 0~25.0)
PID control and associated gain (P).