37
§
CE48
Multi steps function operation reset (settable range0~1)
The function cannot be modified during revolution
Memorized of current operation step and time (in sec) while shut down or power failure.
Step and time reset to 0 when set CE48=1.
Note: External terminal 6 set to RST function, when RST connect with COM, it will reset
the records and steps time to 0.
§
CE49
Multi steps process control continuous operation (settable range0~1)
The function cannot be modified during revolution
Selection of shut down or start from 1
st
step while entire operation procedure finished.
CE49=0 Not continuous operation.
CE49=1 Continuous operation. From 1st steps’ speed continuous operation.
CE49=2 Continuous operation, perform speed as the last speed in the step, till the
RST or CE48 set to1, then change to first step’s speed.
Not continuous
operation
F re q u e n c y
t
F irs t s te p
la s t s te p
Continuous
operation
frequency
t
From 1st step speed
continuous operation.
First step
last step
Continuous
operation, perform
speed as the last
speed in the step,
till the RST or CE48
set to1
fre q u en cy
t
P e rfo rm sp e e d a s th e la st sp e ed in th e ste p ,
till th e R S T o r C E 4 8 se t to 1 , the n ch a n g e
to first ste p ’s spe e d to co n tinu o u s o p e ra tio n
F irst ste p
L a st ste p