42
EXPERT 64+, rev.12
EXPERT 64+
SETTINGS – FOR A CURTAIN BASED ON
THE STATIC PRESSURE
Tunnel Curtain Settings
Exit: Press Back
Change: Press Modify
Press
to select an item
Minimum outside temp.
50.0 °F
Minimum age
1 days
Curtain starts opening
at tunnel Fan Group
3
PreOpening
45 sec
Wind Effect Delay
0:30 (m:s)
PreOpening #2 at Tunnel
15 sec
Close VentDoor at tunnel:
6
Pressure Set Point:
Summer Low
.04 “WC
Summer High
.07 “WC
Winter Low
.04 “WC
Winter High
.07 “WC
Tunnel Probe at Tunnel:
4
Pre-opening Delay —
Set the time that is
required to pre-open the curtain before ac-
tivating the tunnel fans. Adjustable from 0
to 120 seconds.
Wind Effect Delay —
Set the wind effect
delay to the desired value.
Pre-opening #2 at Tunnel —
The opening of
the curtain can be increased when the transi-
tion from lateral and tunnel ventilation is over
(i.e. when the Close Vent Doors at Tunnel
parameter is reached). The pre-opening delay
can be adjusted from 0 to 120 seconds.
Close Vent Doors at Tunnel —
Select the
tunnel fan group at which the vent doors
must close. This temperature signals the
end of the transition from lateral to tunnel
ventilation mode.
Low/High Pressure Limits —
Set the static
pressure level below/above which the tun-
nel curtain opens and closes. If the outside
temperature probe is used, set these limits
separately for winter and summer. *
Seasonal
pressure set points are accessible if the outside
temperature probe is enabled (sec. 4.5.1).
Tunnel Probes at Tunnel —
The average house
temperature becomes based on the average
reading of the tunnel probes at the start-up
of the chosen tunnel fan group.
SETTINGS – FOR A CURTAIN BASED ON
THE TEMPERATURE
Tunnel Curtain Settings
Exit: Press Back
Change: Press Modify
Press
to select an item
Minimum outside temp.
50.0 °F
Minimum age
1 days
Curtain starts opening
at tunnel Fan Group
3
Close Vent Doors at Tunnel
6
Curtain is fully opened
at Tunnel Fan Group:
6
Tunnel Open Times
Tunnel Fan 1
0:30 (m:s)
Tunnel Fan 2
0:30 (m:s)
Tunnel Fan 3
0:30 (m:s)
Tunnel Fan 4
0:30 (m:s)
Tunnel Fan 5
0:30 (m:s)
Tunnel Probe at Tunnel:
4
Close Vent Doors at Tunnel —
The vent doors
fully close at the start-up of the chosen tunnel
fan group. *
This parameter is accessible if vent
doors are enabled (sec. 4.4).
Curtain is Fully Opened at Tunnel Fan Group # —
The curtain fully opens at the start-up of this
tunnel fan group.
Curtain’s Opening Times —
Associate an
opening time to the start-up of each tunnel
fan group. The opening time can be adjusted
from 0 to 15 minutes.
If some tunnel fan groups are pro-
grammed to start running BEFORE tun-
nel ventilation starts, set their curtain’s
opening time to 0m:0s.
Tunnel Probes at Tunnel —
The average house
temperature becomes based on the average
reading of the tunnel probes at the start-up
of the chosen tunnel fan group.