4.6.2. RH Compensation Parameters
1. Select
»
9. Advanced Settings
»
10. Relative Humidity Compensation
* This menu is accessible if the humidity probe is
enabled.
Exit: Press Back
Change: Press Modify
Press
to select an item
RH Compensation Settings
Relative Humidity Compensation
Add Min Vent sec
60 sec
RH Setpoint
65 %
Heater Compensation
Minimum On Time
15 sec
Maximum On Time
45 sec
Cycle Time
300 sec
Mist Shutoff
85 %
Mist On Low % Relative Humidity
Low Setpoint
30 %
On Time
0:30
(m:s)
Off Time
2:00(m:s)
2. Set the following parameters:
Add Min Vent sec —
Time that is added to
the fans’ running time, within the minimum
ventilation cycles, when the relative humidity
exceeds the RH Set Point by 10%. Adjustable
from 15 to 900 seconds in increments of
15 seconds. Select “Off” to deactivate this
function. *
This parameter is accessible if the
RH compensation on the minimum ventilation is
activated.
RH Set Point —
This is the humidity level
above which high RH compensation func-
tions start. Adjustable from 20 to 99% of
humidity (select
Off
to disable all high RH
comp functions). *
This parameter is accessible if
the RH compensation on heaters or on the minimum
ventilation is activated.
Heater compensation
The timer used by heating outputs is made
of an
“On Time”
and of a
“Cycle Time”
. Heating
outputs run during the
“On Time”
then stop
until the end of the
“Cycle Time”
. The
“On
Time”
portion of this cycle increases as RH
levels increase.
Minimum & Maximum On Times —
Set the
minimum and maximum
“On Times”
of the
heating timer. The minimum
“On Time”
starts
being used when indoor humidity levels reach
the RH set point; the maximum
“On Time”
is
used when humidity levels are 10% above
the RH set point. *
This parameter is accessible
if RH compensation with heating outputs is enabled
in section 4.6.
Cycle Time: —
Set the
“Cycle Time”
of the
heating timer. *
This parameter is accessible if RH
compensation with heating outputs is enabled.
Mist Shutoff —
Set the humidity level above
which the cooling outputs stop running. *
This
parameter is accessible if the mist shutoff compensa-
tion function is enabled.
Lo Set Point —
Set the humidity level below
which misting units start running in timer
mode or select
“Off”
to disable this function.
*
This parameter is accessible if the mist on low RH
compensation function is enabled.
On/Off Times —
Set the
“On Time”
and the
“Off Time”
of the misting timer.