20

EXPERT 64+, rev.12

EXPERT 64+

4.7.  Relay Assignment

4.7.1.  Principle of Operation

Relay Panels : 

The controller can activate up 

to 64 On/Off relays; these relays are located 
in external relay boxes. Up to two RP-32 relay 
panels can be connected to the controller. Refer 
to the wiring diagram enclosed with this manual 
to connect relay panels to the controller.

Vent Door & Tunnel Curtain Relays : 

Relays 

13-14,  15-16,  29-30  and  31-32  the  relay 
panels have specially been designed to open/
close the vent doors and the tunnel curtain. 
It is strongly recommend using these relays 
for this specific purpose: this prevents acti-
vating both the OPEN and CLOSE relays, by 
inadvertence, at the same time.

Fan & Tunnel Fan Relays :  
• Timer-based relays: 

Fan groups and tunnel 

fan groups can activate relays that operate 
in timer mode. These relays allow activating 
cooling  devices  such  as  mist  units  while  a 
specific fan/tunnel fan group is running. Se-
lect “TMR” on a relay to use this function.

• Open/close relays: 

Relays can be used to 

slightly open an air inlet at the start-up of a 
fan/tunnel  group  and  to  close  it  when  the 
fan/tunnel fan group returns to a stop. The 
inlet opens only once at the start-up of the 
chosen fan/tunnel fan group and closes only 
once when the group is disabled. The inlet’s 
running time corresponds to the timer-based 
relay’s On Time. Select 

“OPN”

 to assign an 

opening relay or 

“CLO”

 to assign a closing 

relay on a fan/tunnel fan group. 

  1 

  ---  TMR  ---  ---  ---  ---  --- 

  9 

10 

11  12 

13  14 

15  16 

  ---  ---  ---  ---  ---  ---  ---  ---

  17 

18 

19  20 

21  22 

23  24 

  OPN  ---  CLO  ---  ---  ---  ---  ---

Fan Group 1 Relay Assignment

Selected output

This relay will run in timer 

mode when fan group 1 

is active

This relay will 

runs when 

fan group 1 is 

active

This relay switches at the

startup of fan group 1. The

inlet opens once, during

the timer-based relays’

On time.

The relay switches when

fan group 1 returns to a stop.

The inlet closes once, during

the timer-based relays’

On time.

Relays 13-16 and 29-32 of the relay 

panels have been designed to open 

and close actuators (vent doors or 

tunnel curtains).

Содержание EXPERT 64 Plus

Страница 1: ...EXPERT 64 Temperature Controller User s manual...

Страница 2: ...f this product is used in a manner not specified by the manufacturer Every effort has been made to ensure that this manual is complete accurate and up to date The information con tained in it is howev...

Страница 3: ...ols 9 3 2 How to Select Modify the Parameters 10 3 3 Status LEDs 10 4 CONTROLLER SETUP 11 4 1 Time Date 11 4 2 Password 11 4 3 Controller Programs 12 4 3 1 Selecting a Program 12 4 3 2 Copy Paste Prog...

Страница 4: ...5 1 2 Settings 29 5 2 Set Point Ramp 30 5 3 Seasonal Temperatures 31 6 VENTILATION SETTINGS 32 6 1 Minimum Ventilation 32 6 1 1 Principle of Operation 32 6 1 2 Min Ventilation Ramp 33 6 1 2 1 Min Vent...

Страница 5: ...ATING 50 8 LIGHTS 51 9 CLOCK OUTPUTS 54 10 MONITORING FUNCTIONS 55 10 1 Current Conditions 55 10 2 Individual Temperature Probe Readings 55 10 3 History 56 10 4 Monitoring the Animal Age Number 57 11...

Страница 6: ...t spray water on the controller In order to clean the control wipe it with a damp cloth Before servicing or cleaning unit switch power off at service panel and lock the switch disconnecting means to p...

Страница 7: ...cular temperature settings in accordance with the animal age for instance Status LEDs Pilot lights that indicate the status of the controller outputs are located on the faceplate of the controller The...

Страница 8: ...ING INSTRUCTIONS 2 1 Installing the Controller on the Wall Open the latch and lift the cover Remove the black caps located on each of the four mounting holes Mount the enclosure on the wall using four...

Страница 9: ...0V Output Connection It is recommended to use a 18 to 22 AWG wire to connect the devices to the 0 10V outputs This type of output can be used to connect various devices such as lights 3 USER INTERFACE...

Страница 10: ...nd or attic vent CLOSE Turns on when a vent door is closing sidewall and or attic vent TUNNEL CUR TAIN OPEN Turns on when the tunnel curtain is opening CLOSE Turns on when the tunnel curtain is closin...

Страница 11: ...modified as explained below User Password default 1 1 1 1 2 2 2 2 The user mode gives access to the basic functions of the controller The controller automatically returns to the user mode after 15 min...

Страница 12: ...rameters Running program Select the program that must be used by the controller and then press the Enter Modify key to validate 4 3 2 Copy Paste Programs Use the copy paste function to duplicate all p...

Страница 13: ...the proper num ber of cooling outputs 0 to 6 outputs Number of Clocks Enable the proper num ber of clock outputs Adjustable from 0 to 12 outputs Number of Light Programs Enable the proper number of li...

Страница 14: ...rs are enabled above Use Tunnel Curtain Select Yes to enable the tunnel curtain output Curtain Control Select whether the curtain is controlled by the static pressure SP or by the average house temper...

Страница 15: ...te for changes in airflow patterns that can distort the room temperature If the second probe set is enabled in the Installation Setup sec 4 4 you must assign temperature probes to this second probe se...

Страница 16: ...reading of the humidity sensor can adjusted of 3 Static Pressure SP Probe The reading of the static pressure probe can adjusted of 0 030 WC 7Pa Water Meters Set the water flow per pulse of each water...

Страница 17: ...Cycles RH Level 10 RH Set Point Maximum On Time Regular On Time Min Vent Run Time Time added 2 RH Compensation with the Heating Out puts The controller can compensate for high humidity levels by activ...

Страница 18: ...Yes to stop the cooling outputs when the humidity level is too high This parameter is accessible if a cooling output is enabled sec 4 4 Mist on Low R Humidity Select Yes to activate the cooling outpu...

Страница 19: ...ons This parameter is accessible if the RH compensation on heaters or on the minimum ventilation is activated Heater compensation The timer used by heating outputs is made of an On Time and of a Cycle...

Страница 20: ...group is running Se lect TMR on a relay to use this function Open close relays Relays can be used to slightly open an air inlet at the start up of a fan tunnel group and to close it when the fan tunne...

Страница 21: ...ler mode s 4 2 Only the outputs that are enabled in the Setup menu are available sec 4 4 2 Choose the proper relay then select one of the following options The relay is assigned to the output The rela...

Страница 22: ...he controller fails In this case the alarm relay is activated When the alarm relay is activated the normally open contact closes Adjust the Backup Thermostat Warning Each time the house set point vari...

Страница 23: ...ature is defined to continue monitoring the indoor temperature for high temperatures When the indoor temperature reaches the critical high temperature defined as an absolute value an alarm is set off...

Страница 24: ...Age in days Beginning of the flock End of the flock Alarm limit at the end of the flock Alarm limit at the beginning of the flock Water Spill Alarm Limit 4 8 2 4 Static pressure Alarms The controller...

Страница 25: ...of the main breaker is monitored by a probe set the probe temperature over which a breaker temperature alarm must be set off Acces sible if the breaker s monitoring function is enabled in section 4 4...

Страница 26: ...temperature ramp func tion is common to all programs of the controller 1 Select 9 Advanced Settings 9 Critical Alarm Ramping This menu is accessible if an outside temperature sensor is enabled Critic...

Страница 27: ...y Zone s Low Alarm Limit Refer to section 4 8 to set this alarm limit Non Brood Zone Brood Zone Heater Heaters Fans Unused Fans Unused Fans Unused Fans Unused Fans Unused Fans Unused Fans Unused Fans...

Страница 28: ...12 Setup 10 Version EXPERT 64 SETTINGS V X X PROGRAM V X Xx 4 11 Test Mode The test mode is used to simulate changes in the ambient temperature and verify the controller s performance When the test i...

Страница 29: ...pty Zone Set Point is the target room temperature in the empty zones the heating units located in that type of zone operate ac cording to this temperature The empty zone set point also becomes the tar...

Страница 30: ...mperature for each unnecessary step 1 Select 9 Advanced Settings 1 House Temperature Ramping The ramp steps can only be modified while the ramp is disabled sec 5 2 Exit Press Back Change Press Modify...

Страница 31: ...which temperature the summer and winter static pres sure set points start being used This function is available if an outside temperature sensor is activated sec 4 5 1 1 Select 6 Inlet Settings 4 Outs...

Страница 32: ...This timer is common to all programs of the controller Min Vent Fan Status ON OFF Time ON Time Cycle Time Minimum Ventilation Timer Minimumventilationparametersarecom mon to all programs of the contr...

Страница 33: ...ion ramp can be set differently for nighttime minimum ventilation The user must then specify the time at which the night settings start being used 1 Select 9 Advanced Settings 2 Minimum Ventilation Ra...

Страница 34: ...letting the animals enter This parameter can only be modified while the ramp is disabled On Time Assign a minimum ventilation On Time to each step of the night ramp This parameter can only be modifie...

Страница 35: ...tilation the controller can make a rotation of the fans selection between consecutive cycles This rotation allows run ning the fan motors evenly and regularly In order to use fan cycling you must spec...

Страница 36: ...for Cooling Devices Fan Tunnel Fan Groups can activate relays that operate in timer mode This is useful to activate mist units that follow the ventila tion s progression The timer composed of an On T...

Страница 37: ...only sec 4 2 Fan Group Timer Settings Group 1 On Time 0 15 m s Off Time 5 00 m s Group 2 On Time 0 15 m s Off Time 5 00 m s Group 3 On Time 0 15 m s 2 Set the On and Off times of the fan tunnel fan g...

Страница 38: ...tart temperature of the tunnel fan group that causes the closure of vent doors the tunnel ventilation mode is fully used at that moment and the controller starts using the tunnel ventilation s static...

Страница 39: ...me has elapsed or after a 120 second delay whichever is shorter the tunnel fan group is activated The activation of every consecutive tunnel fan group causes the curtain to open further according to t...

Страница 40: ...when the outside temperature is too cold This fea ture is optional and can only be used if an outside temperature sensor is connected to the controller Minimum Age The minimum age is used to prevent t...

Страница 41: ...the outside temperature 6 3 2 2 Curtain Settings 1 Select 6 Inlet Settings 3 Tunnel Curtain 2 Set the following parameters Refer to the previous section to get further informa tion on these parameter...

Страница 42: ...these limits separately for winter and summer Seasonal pressure set points are accessible if the outside temperature probe is enabled sec 4 5 1 Tunnel Probes at Tunnel The average house temperature b...

Страница 43: ...dewall Hi pressure limits The vent doors start closing after the Wind Delay has elapsed The vent doors start opening after the Wind Delay has elapsed The vent doors stop closing The vent doors stop op...

Страница 44: ...t Settings 2 Sidewall vents This menu is available if vent doors are enabled sec 4 4 Sidewall Vent Settings Pressure Set Point Summer Low 05 WC Summer High 08 WC Winter Low 05 WC Winter High 08 WC Win...

Страница 45: ...han the Attic start T temperature value Room T Room T Compens start T Room T Compens start T Room T Compens stop T Attic Compensation on the Minimum Ventilation Timer Compen sated On Time On Time Cycl...

Страница 46: ...fect Delay When the pressure level exceeds the high or low pressure set points the attic vent starts opening or closing continuously right after the wind delay has elapsed The high or low pressure con...

Страница 47: ...g to the average house tempera ture in tunnel ventilation they operate ac cording to the average temperature measured by user defined probes Refer to section 4 5 3 to assign these probes 1 Select 8 ON...

Страница 48: ...t s start temperature Max On Time Off Time Set both tim ers On and Off times to the desired values Adjustable from 0 to 30 minutes Start Stop at The cooling outputs opera tion is only effective within...

Страница 49: ...Time and of a Cycle Time as illustrated ON OFF Output Status Stir Fan Timer Time ON Time Cycle Time Based on the minimum ventilation When they are based on minimum ventilation stir fans are activated...

Страница 50: ...Fire Stop T Heater 1 Hi Fire Start T Heater 1 Start T Heater 1 Stop T T of heater s probes Heaters Hi Fire This option allows to simulate a supplemen tary heating step for each activated heating outp...

Страница 51: ...er This parameter is accessible for the heaters that operate in empty zones sec 4 9 1 8 LIGHTS The controller has two 0 10V outputs to con trol lights a LD 7000 light dimmer module can be connected to...

Страница 52: ...d Intensity 80 Use light peaks Yes Peak Cycle 0 15 h m Peak Duration 1 min Peak Intensity 100 Peak Sunrise 2 min Peak Sunset 2 min 2 Set the following parameters Day This is the day at which the selec...

Страница 53: ...hts on 24 hours option is disabled above Stop Time Set the time at which the light intensity starts decreasing sunset Acces sible if the lights on 24 hours option is disabled above Standard Intensity...

Страница 54: ...me e g 9h00AM On Off Off Note that the Start Run mode allows stop ping the outputs with a little more precision since it allows stopping them by the seconds contrarily to the Start Stop mode which al...

Страница 55: ...C is applied on the house set point the warning message Adjust Backup Thermostats prompts on screen Select Yes to clear this message once the backup thermostats have properly been adjusted 10 2 Indiv...

Страница 56: ...ature probe is enabled sec 4 5 1 Relative Humidity The daily min max readings of the humidity probe are displayed for the past 75 days Accessible if the humidity probe is enabled sec 4 5 1 Static Pres...

Страница 57: ...eset when a new batch starts ALL of histories are reset when a new batch starts 1 Select 3 Animal Age Mortality Exit Press Back Press to select an item Animal Age Mortality Animal Age 5 days Initial C...

Страница 58: ...culled animals Total Mortality This is the total number of mortalities since the beginning of the batch This value is displayed as a reading and can not be modified Total Culled This is the total numb...

Страница 59: ...Outputs 12 Vdc 10 regulated 350 mA max Alarm Contact 24 Vac or dc max 0 15 A Enclosure ABS moisture and dust tight Operating temperature 32 to 104 F 0 to 40 C Storage temperature 5 to122 F 15 to 50 C...

Страница 60: ...ommunication speed to the desired value select the high speed mode if the controller uses the A BOX communi cation system or select the low speed if it uses AGNET 4 Simultaneously press and hold the r...

Страница 61: ...e root of the USB drive It cannot access any sub directory 2 Control MemStick Choose 2 Control MemStick to save your controller settings on the USB drive The saving process will start as soon as you e...

Страница 62: ......

Страница 63: ...___________________________________________________________ Fax ____________________________________________________________ INSTALLER Name ____________________________________________________________...

Страница 64: ...on to all programs Static pressure WC Pa Common to all programs 3 RH COMPENSATION 4 6 On minimum ventilation Yes No On heaters Yes No Using the mist shutoff Yes No Use mist on low RH Yes No 4 INSTALLA...

Страница 65: ...e attic probe Yes No Use Tunnel curtain Yes No Curtain control T SP Use tunnel probes at tunnel fan 0 16 Number of relays 32 40 42 56 64 relays Common to all programs Monitor the breaker tempera ture...

Страница 66: ...Cooling 5 Cooling 6 Heater 1 Heater 1 Hi Fire Heater 2 Heater 2 Hi Fire Heater 3 Heater 3 Hi Fire Heater 4 Heater 4 Hi Fire Heater 5 Heater 5 Hi Fire Heater 6 Heater 6 Hi Fire Heater 7 Heater 7 Hi Fi...

Страница 67: ...4 Tunnel Fan Group 5 Tunnel Fan Group 6 Tunnel Fan Group 7 Tunnel Fan Group 8 Tunnel Fan Group 9 Tunnel Fan Group 10 Tunnel Fan Group 11 Tunnel Fan Group 12 Tunnel Fan Group 13 Tunnel Fan Group 14 Tun...

Страница 68: ...5 6 Tunnel Fan Group 1 Tunnel Fan Group 2 Tunnel Fan Group 3 Tunnel Fan Group 4 Tunnel Fan Group 5 Tunnel Fan Group 6 Tunnel Fan Group 7 Tunnel Fan Group 8 Tunnel Fan Group 9 Tunnel Fan Group 10 Tunn...

Страница 69: ...rev 12 EXPERT 64 Relay Assignment Worksheet Rel Relay function Prog 1 Prog 2 Prog 3 Prog 4 Prog 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37...

Страница 70: ...70 EXPERT 64 rev 12 EXPERT 64 Rel Relay function Prog 1 Prog 2 Prog 3 Prog 4 Prog 5 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 Relay Assignment Worksheet...

Страница 71: ...hile doing so lift the card upwards with your index fingers 2 Pull the card out of its connector Inserting a Core Card Before proceeding switch power off at service panel and lock the switch disconnec...

Страница 72: ...s calibration 16 Card Memory card 60 Clean Mode see also Empty zones Principle of operation 27 Settings 27 Clock Setting the time and date 11 Clock outputs Operation settings 54 Relay assignment 21 S...

Страница 73: ...obe assignment 15 16 Relay assignment 21 RH compensation see Relative humidity 17 Run times 56 Hi Lo Fire see Heaters History 56 House set point see Temperatures House temperature see T Humidity see R...

Страница 74: ...30 Minimum ventilation s On Time ramping Operation 33 Settings 33 Relative humidity RH Activating the RH probe 14 History 56 RH Compensation Activation 18 Principle of operation 17 18 Settings 19 RH...

Страница 75: ...ration 36 Probe selection 15 16 Tunnel ventilation Principle of operation 39 40 Tunnel curtain Based on the house T Activation 14 Principle of operation 39 Settings 41 Based on the pressure level Prin...

Страница 76: ...M 890 00077 rev 12 REV 07...

Отзывы: