5.2. Set Point Ramp
The temperature ramp function allows an au-
tomatic adjustment of the house set point over
time, in accordance with the animals needs.
The house set point changes using 10 steps.
Each step specifies a day number and a target
temperature for that day. These steps refer
to the animal age. Once all steps are defined,
the ramping function must be activated. The
controller then starts changing the house set
point every hour in a linear fashion between
consecutive steps of the ramp. When the last
step is reached, the house set point for that
day is maintained until the end of the flock.
Set Point
90.0
87.2
84.4
81.6
78.8
76.0
73.2
70.4
67.6
64.8
62.0
1 5 10 14 19 24 28 33 38 42 47 Day
Set Point Ramp
NOTE
: Certain restrictions apply to reduce
the risk of errors:
- The highest possible day number is 450.
- Decreasing day numbers is not allowed.
- All ten steps must be specified. If you don’t
need ten different steps, repeat the last
temperature for each unnecessary step.
1. Select:
»
9. Advanced Settings
»
1. House Temperature Ramping
The ramp steps can only be modified
while the ramp is disabled (sec. 5.2).
Exit: Press Back
Change: Press Modify
Press
to select an item
House Temperature Ramping
House Temp.
70.0°F
day -5
78.0°F
day 0
75.0°F
day 5
70.0°F
day 10
65.0°F
day 15
63.0°F
day 20
61.0°F
day 25
60.0°F
day 30
60.0°F
day 35
60.0°F
day 40
60.0°F
Ramping Status: Off
2. Set the following parameters:
(Refer to the previous section to get further informa-
tion on these parameters)
Day numbers —
Set the day at which each
step starts. The day number refers to the
animal age. It is adjustable from -5 to 450
days. Negative values are used to prepare
the house before letting the animals enter.
*
This parameter can only be modified while the
ramp is disabled.
Temperature —
Assign a temperature set
point to each step of the ramp. *
This parameter
can only be modified while the ramp is disabled.
Status —
Select
“Yes”
to activate the ramp.
Once the ramp is on, the controller auto-
matically adjusts the set point automatically
between consecutive points of the ramp; for
this reason, ramp steps cannot be modified
while the ramp is running.