37
EXPERT 64+, rev.12
EXPERT 64+
6.2.2. Settings
1. Select:
»
8. ON / OFF Temperature
»
(3. or 4.) Fan / Tunnel Fan Group
2. Set the following parameters:
Fan Groups ON / OFF Temp.
House Set Point
70.0 °F
Fan 1 ON
72.0 °F
OFF
71.0 °F
Fan 2 ON
74.0 °F
OFF
72.0 °F
Start & Stop Temperatures —
Set the start
and stop temperatures of each fan/tunnel fan
group. It is suggested to leave a gap of at
least 0.5°F (0.3°C) between the start-up of
each group.
6.2.3. Timer-based Relays
1. Select
»
12. Setup
»
7. Relay assignment*
»
(11. or 12.) Fan / Tunnel Fan
»
Timer Settings
* This menu is accessible from the installer mode
only (sec. 4.2).
Fan Group Timer Settings
Group 1 On Time
0:15 (m:s)
Off Time
5:00 (m:s)
Group 2 On Time
0:15 (m:s)
Off Time
5:00 (m:s)
Group 3 On Time
0:15 (m:s)
2. Set the On and Off times of the fan/tunnel
fan groups’ timer-based relays. Refer to the
previous section to get further information
on this function.
6.2.4. Fan Group Shutoff in Transi-
tional Ventilation
1. Select:
»
9. Advanced Settings
»
6. Fan group shut off
»
Select the desired tunnel fan group
1
2
3
4
5
--- --- --- --- ---
Fan group shutoff in tunnel 1
2. Select which fan group needs to be dis-
abled when the selected tunnel fan group
starts up. In the example beside, the acti-
vation of Tunnel Fan Group 1 causes the
deactivation of Fan Group 2.
A worksheet is available at the end of
this manual to write down your fan
shutoff parameters.