Page 54
very quick when there are many Areas associated with a keypad because up to 7 Area numbers
can be displayed per line. If the option is turned Off the Armed Areas will be displayed with the full
Area name. This is useful if there are only a couple of Areas associated with a keypad.
Option 7
Double Badge to ARM Keypad -
If this option is turned on and an access card/tag with Arm/
Disarm capabilities is used at this reader/keypad, the access card/tag will always disarm the
associated area from the arm state but when disarmed the first presentation of the card/tag will
start a 10 second timer which will allow the same card/tag to be presented a second time within
10 seconds to arm the area.
Option 8
Control button operates output directly -
If this option is turned on for the associated keypad
then pressing the CONTROL button for 1 second will turn on all outputs assigned at addresses
P34E option 7 and P83E. If it is turned off pressing the CONTROL button for 1 second will take
the user to the output control menu where individual output numbers can be entered to turn
outputs on or off singularly.
BULK COPY A KEYPAD TO A RANGE OF KEYPADS
Bulk COPY a Keypad to a range of Keypads
- P97E
It is possible to set up a single Keypad and then copy the programmed data for that keypad to a range of keypads.
For example if Keypad 15 was set up as a template and that data was required to be copied to Keypads 16 to 20
inclusive then once keypad 15 has been fully programmed by entering in P97E 15E followed by 16E then 20E the
panel will copy Keypad 15’s settings to all keypads from 16 to 20. This process can be repeated many times with
different Keypads set up as a template and a different range of keypad addresses.
PROXIMITY READER LED to OUTPUT MAPPING
PROXIMITY READER LED to OUTPUT MAPPING -
P98E 1-32E Value = 01-32 for Outputs 1-32
Option 01 = Proximity Reader LED follows Output 1 - Option 32 = Proximity Reader LED follows Output 32
If a proximity reader is connected to the control panel via the Wiegand Interface it may be desirable to have the LED
provide some form of indication such as Arm/Disarm state, etc. By using this location it is possible to link the LED at
a reader number to follow the programming of an output. The LED can be used to indicate Arm/Disarm state, Stay
Mode Arm/disarm, output On/Off, etc. If chirps have been assigned to access tags/cards (P46E4E) and the output
the reader LED is set to follow has the chirps assigned (P50E-P53E), then the output must have a minimum pulse
time (P39E) of 10 for it to work correctly.
PROGRAM FULL LCD KP “KEYPAD” NAME
Program FULL LCD KP “Area” Name Text
- P100E
1-32E
Each Keypad can have a custom name that will be displayed when in Memory Mode. The FULL LCD KP “Keypad”
name text is programmed at this location. If option 3 is Off at P96E then this name will be the idle display name on
the keypad.
+++++Zones+++++
BULK COPY A ZONE TO A RANGE OF ZONES
Bulk COPY a Zone to a range of Zones
- P118E
It is possible to set up a single Zone and then copy the programmed data for that zone to a range of zones. For
example if Zone 20 was set up as a template and that data was required to be copied to Zones 21 to 30 inclusive
then once zone 20 has been fully programmed by entering in P118E 20E followed by 21E then 30E the panel will
copy Zone 20’s settings to all zones from 21 to 30. This process can be repeated many times with different Zones set
up as a template and a different range of zone addresses.
GLOBAL ZONE EOL (End-of-Line) OPTIONS
There are 8 hardwired zone inputs on the panel with up to 64 zones in total via the input expanders. Each of these
inputs can have different EOL (End-of-Line) configurations if desired. To do that the value at P119E 1E must be set
to 0 so that address P125E can set individual values for each zone from type 0-13. If the value at P119E 1E is set to
1-16 this sets all zones to be that value and the value at P125E cannot be changed. See chart on page 11 for the
resistor combinations and colour codes.