STAY MODE EXIT DELAY TIME
STAY MODE EXIT DELAY TIME -
P61E 1-32E (1 = Area 1, 32 = Area 32) (Value 0-255 Seconds)
Each Stay Mode Area can have their own exit delay time. The delay can be programmed from 1-255 seconds in one
second increments. If the exit delay is set to “0” the panel will be instantly armed.
MONITORING ACCOUNT CODE NUMBER
MONITORING ACCOUNT CODE NUMBER -
P62E 1-32E (1 = Area 1, 32 = Area 32) (Value 0000-FFFF)
When the dialler is reporting to a monitoring station there must be a unique account code programmed to identify the
panel. There is an account code for each area. The account code is 4 digits. Each digit can be a number from 0-9 as
well as the special characters B,C,D,E & F. The chart below shows how the special characters are entered.
DTMF REMOTE CONTROL CODE NUMBER
DTMF REMOTE CODE NUMBER -
P63E 1-32E (1 = Area 1, 32 = Area 32) (Value 1-4 digit code 0-9999)
The panel can be configured to allow remote Arm/Disarm of each Area via a remote telephone. The codes
programmed at this address are the DTMF code that must be used when performing this function. When dialling the
panel and it has answered the call, after the audio prompt to enter your code enter in the 1-4 digit DTMF code
followed by the # key and the current status will be given of the Area associated with the code entered. After that, if
you press the “*” key on the telephone the status of the area will toggle eg if is was previously armed it will change to
disarmed or vice versa. When finished you simply hang-up and 15 seconds later the panel will release the line.
START OF “DTMF ARM/DISARM” STATUS MESSAGES
START OF “DTMF ARM/DISARM” STATUS MESSAGES
- P64E 1-32E (1 = Area 1, 32 = Area 32) (0-99)
Reserved for future use.
ARMED EXIT BEEPS to OUTPUT
ARMED EXIT BEEPS to OUTPUT -
P65E 1-32E (1 = Area 1, 32 = Area 32)
Value = 01-32 for Outputs 1-32
Option 01 = Output 1 - Option 32 = Output 32
Sometimes it can be useful to have an exit delay indication on an audible device on the exit path. This option allows
the exit delay during arming to be assigned to any of the 32 outputs. The Output would normally turn on and stay on
during the whole exit delay however if Option 6 at P37E is turned on the output will pulse at the pulse timer rate
(P39E) during the exit delay. Also if arming on a Time-zone or no activity is set, and the pre-alert timer is active, this
option will cause the output to turn on for 1 second and off for 5 seconds to indicate that arming will happen if no
zones are triggered. The pre-alert output signal has been engineered to be different to the exit delay signal so users
can tell which timer is running. Outputs 1 & 2 have additional special functions when set to siren outputs (P37E
option 1 ON). When output 1 or 2 are set to be a siren output, with an 8ohm speaker attached, they will sound a 1khz
tone during the pre-alert timer period (on for 1 second, off for 5 seconds) and pulse the 1khz tone at the pulse timer
rate during exit delay. These two audible indications are controlled by the volume setting (P33E) so the sound can be
set to a comfortable level. If an alarm occurs using the same output the siren tone will be at full volume. Finally to
further differentiate between the pre-alert and exit delay indications the door bell chime can be programmed at P36E
LCD KEYPAD BUTTON
ACCOUNT CODE SPECIAL CHARACTERS
CONTROL & 0
DELETE
CONTROL & 2
“B”
CONTROL & 3
“C”
CONTROL & 4
“D”
CONTROL & 5
“E”
CONTROL & 6
“F”