Page 36
automatically adjust for daylight saving.
NOTE:
If the start and/or stop Sunday (P27E above) must be the last Sunday of the month (which can be Sunday
number 4 or 5 depending on the year) then you must se the value to 5.
+++++++++
NOTE: With all output programming options we refer to outputs 1-32. Only outputs 1-4 are available as
standard, outputs 5-32 require the connection of the optional 4 way output expander boards.
BULK COPY AN OUTPUT TO A RANGE OF OUTPUTS
Bulk COPY an Output to a range of Outputs
- P30E
It is possible to set up a single Output and then copy the programmed data for that output to a range of outputs. For
example if Output 2 was set up as a template and that data was required to be copied to Outputs 3 to 8 inclusive then
once output 2 has been fully programmed by entering in P30E 2E followed by 3E then 8E the panel will copy Output
2’s settings to all outputs from 3 to 8. This process can be repeated many times with different Outputs set up as a
template and a different range of output addresses.
Program LCD KP “Output” Name
Program LCD KP “Output” Name Text -
P31E 1-32E
Each output can have a custom name that will be displayed when in Memory Mode. The FULL LCD KP “Output”
name text is programmed at this location.
Program Output Volume when Disarmed
O/P 1 & 2 Volume when the alarm is disarmed -
P33E 1-2E Value = 1-8
If Outputs 1 or 2 are programmed as siren outputs (P37E option 1 on) and have an 8 ohm speaker connected to an
output the speaker can produce quieter sounds when Disarmed but full volume sounds when armed. The Volume of
O/P 1 & 2 when the alarm is disarmed can be set to a value of 1-8, 1 being the quietest and 8 being the loudest. This
is useful for things like 24 hour smoke alarms which can sound at a lower volume when disarmed but sound at full
volume when armed. Also if a day zone triggers output 1 or 2 the output will produce a door bell sound and the
volume of the door bell can be adjusted using this address.
OUTPUT OPTIONS “A”
OUTPUT OPTIONS “A”
- P34E 01-32E
Option 1 - Invert Output
Option 2 - Flash Output
Option 3 - Single Pulse to Output
Option 4 - Lockout Output
Option 5 - DTMF Remote Control of Output
Option 6 - Keypad User can Operate Output
Option 7 - <CONTROL> button can Operate Output
Option 8 - Pulsed Chime Alarm (linked to pulse timer)
Option 1
Invert Output
- This option is used to invert the normal state of the output. The panel uses open drain
FET switches and the default state of all outputs is off (open). When in alarm the FET is turned on and
the output goes low (0V). The invert option reverses this function.
Option 2
Flash Output
- When the output is turned on this option causes the output to flash at a rate set by the
pulse timer (P39E). One use is to flash a lamp during an alarm. DO NOT turn this option on if the Output
is to be manually controlled by a user or the “Control” button.
Option 3
Single Pulse to Output
- This option produces a single pulse at the output when an alarm occurs (the
pulse time is the value programmed at the output pulse timer P39E).
Option 4
Lockout Output
- This option is used to limit the output to one operation per arming period.
Option 5
DTMF Remote Control of Output -
If the panel is set-up so a User can dial in from a remote telephone
to perform “DTMF Code Control” (P175E12E) of the Outputs, this option selects which Outputs are able
to be controlled by the remote user.
Option 6
Keypad User can Operate Output
- If a DTMF Output control code is programmed into the panel
(P175E12E), the same code can be entered at the panel keypad to allow local control of the Outputs