ZONE OPTIONS B
ZONE OPTIONS B
- P123E 1-64E Value 1-8
Option 1 - Zone is a Handover Zone
Option 2 - Zone is a Two Trigger Zone
Option 3 - Zone is a 24 Hour Zone
Option 4 - Zone is an Auto-reset Zone
Option 5 - Zone is a 24 Hour Fire Zone
Option 6 - Zone is shared (Off = not shared)
Option 7 - Zone is a Chime Zone
Option 8 - Zone is a Permanent Chime Zone
Option 1
Zone is a Handover Zone
- A Handover Zone is one that its entry delay will apply provided a Non-
Handover entry zone is triggered first. If no other entry delay zones are triggered before the handover
zone the entry delay on that zone does not apply and the alarm will become instant (no entry delay).
Option 2
Zone is a Two Trigger Zone
- If this option is on the zone will have to trigger twice within the two
trigger time (P25E5E) before it will cause an alarm. If the zone does not trigger a second time before
the two trigger time expires, the count is reset and it will take another two triggers to cause an alarm on
this zone. If more than one zone is set-up as a two trigger zone, then a single trigger from two separate
two trigger zones within the two trigger time can also cause an alarm. If the zone becomes faulty and
stays in alarm once triggered it will also cause an alarm provided it remains in alarm for longer than the
two trigger time.
Option 3
Zone is a 24 Hour Zone
- If this option is on the zone will be constantly monitored regardless of the
arm/disarm state of the panel. If the 24 Hour zone also has an entry delay programmed (P144E), this
delay will apply. If the 24 Hour zone activates but then resets before the entry delay expires no alarm
will be generated. This feature can be useful for monitoring plant type alarms such as freezer alarms.
Once the alarm has been generated it must be cleared by entry of a valid User code.
Option 4
Zone is an Auto-reset Zone
- If this option is on the zone will activate only when the associated area
is armed. If the Auto-reset zone also has an entry delay programmed (P144E), this delay will apply. If
the Auto-reset zone is activated during the armed state but then resets before the entry delay expires
no alarm will be generated. Once an alarm has been generated with an Auto-reset zone the alarm will
be removed automatically once the input reseals (Auto-reset). If options 3 & 4 are turned on together
the zone will work as a 24 Hour Auto-Reset zone.
Option 5
Zone is a 24 Hour Fire Zone
- If this option is on the zone will be constantly monitored regardless of
the arm/disarm state of the panel. If the 24 Hour Fire zone also has an entry delay programmed
(P144E), this delay will apply. If the 24 Hour Fire zone activates but then resets before the entry delay
expires no alarm will be generated. Once the alarm has been generated it must be cleared by entry of
a valid User code. The 24 Hour Fire Zone will also cause an alarm output to pulse the alarm to
differentiate a fire alarm from a burglar alarm (ie a fire alarm will switch the output on and off at the
pulse timer rate whereas a burglar alarm on the same output will sound continuously).
Option 6
Zone is Shared
- If this option is On the zone is “Shared”. That means if the zone is in multiple Areas it
will not go into alarm unless all assigned areas are armed. If the zone does go into alarm it will report
to the lowest assigned area number (only one alarm will be sent). If the option is Off the zone is no
longer shared. That means the zone will go into alarm if any of the assigned areas are armed. It also
means that it will send an alarm for every area that is armed.
Option 7
Zone is a Chime Zone
- If this option is on, the zone will operate Chime mode when disarmed. When
the alarm is armed the Chime Mode is disabled for this zone. A Chime zone can sound the keypad
buzzer or operate an output to indicate that the zone is unsealed. It is normally used to monitor areas
during the daytime.
Option 8
Zone is a Permanent Chime Zone
- If this option is on, the zone will operate Chime mode when
armed or disarmed. When the alarm is armed the zone will continue to only be a Chime Mode Zone
and will not cause a burglar alarm. A Chime zone can sound the keypad buzzer or operate an output to
indicate that the zone is unsealed.
ZONE OPTIONS C
ZONE OPTIONS C
- P124E 1-64E Value 1-8