MFR_OT_FAULT_COUNT
[F2h]
Read
It reads the number of times stopping by the overheating protection feature.
Note1: For clear the count, use MFR_CLEAR_FAULT_COUNT [ F5h ].
Note2: For saving count, don't block the input voltage, between 100ms output voltage is stopped.
Display format
: Linear(Count)
Initial setting
: 0 [ times ]
Range of setting and reading
: 0 - 255 [ times ]
MFR_UT_FAULT_COUNT
[F3h]
Read
It reads the number of times stopping by the undertemperature feature.
Note1: For clear the count, use MFR_CLEAR_FAULT_COUNT [ F5h ].
Note2: For saving count, don't block the input voltage, between 100ms output voltage is stopped.
Display format
: Linear(Count)
Initial setting
: 0 [ times ]
Range of setting and reading
: 0 - 255 [ times ]
MFR_TON_MAX_FAULT_COUNT
[F4h]
Read
It reads the number of times stopping by the activation time exceeding protective function.
Note1: For clear the count, use MFR_CLEAR_FAULT_COUNT [ F5h ].
Note2: For saving count, don't block the input voltage, between 100ms output voltage is stopped.
Display format
: Linear(Count)
Initial setting
: 0 [ times ]
Range of setting and reading
: 0 - 255 [ times ]
MFR_CLEAR_FAULT_COUNT
[F5h]
Send
It resets the number of times stopping by the protective function.
Note1: After command transmission, do not shutdown the input voltage for more than 1 second.
Display format
: -
Initial setting
: -
Range of setting and reading
: -
It reads the number of times stopping by protection operation for over start-up time.
1
1
It reads the number of times stopping by the overtemperature fault.
It reads the number of times stopping by the undertemperature fault.
1
bit7-0
00000000
bit7-0
00000000
00000000
bit7-0
Overview
#
bit
value
Overview
#
bit
value
Overview
#
bit
value
Applications manual
For CHS300/400/500-
I
series
- 54 -