MFR_UT_RESTART_LIMIT
[E4h]
R/W Word
It does the setting of the return threshold of the undertemperature and a reading.
In the case of automatic restart mode, it does an automatic-restart, when the temperature of the
detecting-element exceeds this threshold.
Display format
: Linear(Temp)
Initial setting
: -40 [
℃
]
Range of setting and reading
: -45 - 20 [
℃
]
MFR_VOUT_OV_FAULT_COUNT
[F0h]
Read
It reads the stop number of times by the overvoltage protection feature.
Note1: For clear the count, use MFR_CLEAR_FAULT_COUNT [ F5h ].
Note2: For saving count, don't block the input voltage, between 100ms output voltage is stopped.
Display format
: Linear(Count)
Initial setting
: 0 [ times ]
Range of setting and reading
: 0 - 255 [ times ]
MFR_VOUT_UV_FAULT_COUNT
[F1h]
Read
It reads the number of times stooping by the low voltage protection feature.
Note1: For clear the count, use MFR_CLEAR_FAULT_COUNT [ F5h ].
Note2: For saving count, don't block the input voltage, between 100ms output voltage is stopped.
Display format
: Linear(Count)
Initial setting
: 0 [ times ]
Range of setting and reading
: 0 - 255 [ times ]
It reads the number of times stopping by the output undervoltage fault.
1
value
Overview
#
bit
value
Overview
It reads the number of times stopping by the output overvoltage fault.
bit
bit7-0
00000000
1
bit7-0
00000000
#
Applications manual
For CHS300/400/500-
I
series
- 53 -