EXPANSION BOARD CONNECTIONS
Superterm CIC1800 / CICP1400UL
64
DI/DO Alarm Input Connections
The DI/DO board provides eight non-supervised
alarm inputs (see Figure 43).
The eight non-supervised alarm inputs are
connected to the DI/DO board through the Alarm
Input terminal strip.
Table 44 lists the connections to the Alarm Input
terminal strip and the appropriate functions of each
connection.
Table 44 - Alarm Input Terminal Strip
Connection Table
Alarm Input Terminal
Strip
Pin #
Function
1
Alarm 8 Signal
2
Alarm 8 Return
3
Alarm 7 Signal
4
Alarm 7 Return
5
Alarm 6 Signal
6
Alarm 6 Return
7
Alarm 5 Signal
8
Alarm 5 Return
9
Alarm 4 Signal
10
Alarm 4 Return
11
Alarm 3 Signal
12
Alarm 3 Return
13
Alarm 2 Signal
14
Alarm 2 Return
15
Alarm 1 Signal
16
Alarm 1 Return
DI/DO Alarm Cable Requirements
Alarm inputs require 22AWG, 2-conductor,
stranded, shielded cable with drain wire. DO NOT
use twisted pair cables.
NOTES: Route all cables between the Expansion
1/O boards and the Superterm circuit board through
the wire guides provided on the Superterm cabinet.
Cable length between the DI/DO board and an
alarm device is limited to a maximum of 1000 ft
(305m).
Table 45 lists the cable gauge-vs-length
requirements for proper operation of the DI/DO
board and the alarm device.
Table 45 -- Cable Requirements for Alarm
Inputs
Unit Distance
(maximum)
Wire Gauge
Alarm
Device
1000 ft/305m
22AWG Shielded
w/drain
NOTE: All alarm input cables must be grounded.
Refer to the Grounding Accessory Drain and
Shield Wire section, Page 9.
Содержание SUPERTERM CIC1800
Страница 27: ...Figure 15 Superterm Circuit Board Relay Location...
Страница 29: ...RELAY CONNECTIONS Superterm CIC1800 CICP1400UL 29 Figure 16 LOCAL and REMOTE Power Configurations...
Страница 53: ...Figure 34 COM1 Terminal Strip Connection...
Страница 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Страница 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Страница 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Страница 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Страница 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Страница 73: ...SETTINGS Superterm CIC1800 CICP1400UL 73 Figure 46 232 1 EOL1 and EOL2 Jumper Locations and Settings...
Страница 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Страница 77: ...Figure 48 Jumper Locations and Settings...
Страница 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Страница 83: ...Figure 53 256K Memory Upgrade Installation...
Страница 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...