COMMUNICATION CONNECTION
Superterm CIC1800 / CICP1400UL
48
RS-422 to RS-422 REPEAT Network
If the first Superterm in a network is more than 50
feet (15.2m) from the host computer, the polling
line from the host computer must use RS-422
standards.
A Continental Instruments RS-422 Polling Line
Converter may be used at the host computer to
convert RS-232 to RS-422.
Figure 32 shows the required connections for an
RS-422-toRS-422 REPEAT network.
Table 32 lists the necessary connections between:
A host computer and the first Superterm in the
network,
and
The first Superterm in the network and the
remaining Superterm (62 maximum) in a
network.
RS-422 to RS-422 REPEAT Drain Wires
Ground the drain wires for all RS-422 cables in the
network at each individual Superterm in the
network.
RS-422 to RS-422 REPEAT Jumper Setting
Operating a Superterm network in the REPEAT
mode requires setting the MODE 1 jumper and the
EOL2 jumper.
Refer to page 70 for information regarding setting
the MODE1 jumper.
Refer to page 66 for information regarding setting
the EOL2 jumper.
Table 32 - RS-422 to RS-422 REPEAT Network Connections
Host Computer
Superterm #1
Superterm #2
Superterm 3#
Superterm #4
next Superterm
MODE1 jumper= RPT
MODE1 jumper= RPT
MODE1 jumper= RPT
MODE1 jumper= RPT
MODE1 jumper= RPT
Signal
EOL2 jumper = IN
Connector/Pin
EOL2 jumper = IN
Connector/Pin
EOL2 jumper = IN
Connector/Pin
EOL2 jumper = IN
Connector/Pin
EOL2 jumper = IN
Connector/Pin
RS-422 TXD+
RS-422 TXD-
RS-422 RXD+
RS-422 RXD-
POLL 13 (MD/R+)
POLL 14 (MD/R-)
POLL 11 (MD/T+)
POLL 12 (MD/T-)
POLL 7 (RPT/T+)
POLL 8 (RPT/T-)
POLL 9 (RPT/R+
POLL 10 (RPT/R-)
POLL 13 (MD/R+)
POLL 14 (MD/R-)
POLL 11 (MD/T+)
POLL 12 (MD/T-)
POLL 7 (RPT/T+)
POLL 8 (RPT/T-)
POLL 9 (RPT/R+)
POLL 10 (RPT/R-)
POLL 13 (MD/R+)
POLL 14 (MD/R-)
POLL 11 (MD/T+
POLL 12 (MD/T-)
POLL
7
(RPT/T+)
POLL 8 (RPT/T-)
POLL 9 (RPT/R+)
POLL 10 (RPT/R-)
POLL 13 (MD/R+)
POLL 14 (MD/R-)
POLL 11 (MD/T+)
POLL 12 (MD/T-)
>>>>
>>>>
>>>>
>>>>
Содержание SUPERTERM CIC1800
Страница 27: ...Figure 15 Superterm Circuit Board Relay Location...
Страница 29: ...RELAY CONNECTIONS Superterm CIC1800 CICP1400UL 29 Figure 16 LOCAL and REMOTE Power Configurations...
Страница 53: ...Figure 34 COM1 Terminal Strip Connection...
Страница 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Страница 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Страница 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Страница 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Страница 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Страница 73: ...SETTINGS Superterm CIC1800 CICP1400UL 73 Figure 46 232 1 EOL1 and EOL2 Jumper Locations and Settings...
Страница 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Страница 77: ...Figure 48 Jumper Locations and Settings...
Страница 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Страница 83: ...Figure 53 256K Memory Upgrade Installation...
Страница 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...