EXPANSION BOARD CONNECTIONS
Superterm CIC1800 / CICP1400UL
60
Supervised Alarm Board Accessory
Connections
The Supervised Alarm board provides terminal
strips for 16 alarm inputs. The alarm inputs are
connected to the Supervised Alarm board using
connectors J4 through J19 (see Figure 40).
NOTE: Route all cables between the Supervised
Alarm boards and the accessory alarm inputs
through the wire guides provided on the Superterm
cabinet.
Table 41 lists the connections between the
Supervised Alarm board and the alarm inputs.
Table 41 - Accessory Input Connection Table
Supervised Alarm Board
Connector J4-J19
Pin #
Function
1 Alarm
Signal
2 Alarm
Return
NOTE: Alarm connections are not sensitive to
polarity.
CAUTION
A When powering-up the Superterm system, at
least one of the supervised alarm inputs must be
in a non-open condition. The Superterm will
not be able to initialize the Supervised Alarm
board if all of the inputs are open.
Supervised Alarm Cable Requirements
Alarm inputs require a 22AWG, 2-conductor,
stranded, shielded cable with drain wire between
the alarm sensor and the Supervised Alarm board.
DO NOT use twisted pair cable.
Table 42 lists the cable gauge-vs-length
requirements for proper operation of the
Supervised Alarm board and the alarm sensor
device.
Table 42 - Cable Requirements for Alarm
Inputs
Unit Distance
(maximum)
Wire Gauge
Supervised
Alarm
Input
1000 ft/305m
22AWG Shielded
w/drain
NOTE: All alarm input cables must be grounded.
Refer to the section on Grounding Accessory Drain
and Shield Wires, Page 9.
Supervised Alarm Board Address Selection
Jumper
Proper operation of the Superterm and any
Expansion I/O boards requires that each Expansion
1/O board have a unique address.
The Supervised Alarm board has an on-board
Address Selection jumper that identifies the board
to the Superterm (see Figure 40).
Setting the Address Selection Jumper
The I/O signal definitions (numbers assigned to
inputs and outputs) are determined by the
Expansion 1/O board address settings. Refer to the
section on 1/0 Signal Mapping, page 62).
1)
Install all of the Expansion 1/0 boards in the
Superterm Cabinet before setting the Address
Selection jumper.
2)
Determine the location of the Expansion I/O
board in the order,
from right to left,
that the
Expansion I/O boards are mounted (see Figure
40).
3)
Set the Supervised Alarm board Address
Selection jumper accordingly.
NOTES:
The Address Selection jumper has four
possible positions, X1, X2, X3, and X4. Position
X4 is reserved for future use.
Do NOT
use position X4 when setting the Address
Selection jumper.
Figure 39 - Expansion Board Address Positions
Содержание SUPERTERM CIC1800
Страница 27: ...Figure 15 Superterm Circuit Board Relay Location...
Страница 29: ...RELAY CONNECTIONS Superterm CIC1800 CICP1400UL 29 Figure 16 LOCAL and REMOTE Power Configurations...
Страница 53: ...Figure 34 COM1 Terminal Strip Connection...
Страница 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Страница 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Страница 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Страница 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Страница 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Страница 73: ...SETTINGS Superterm CIC1800 CICP1400UL 73 Figure 46 232 1 EOL1 and EOL2 Jumper Locations and Settings...
Страница 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Страница 77: ...Figure 48 Jumper Locations and Settings...
Страница 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Страница 83: ...Figure 53 256K Memory Upgrade Installation...
Страница 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...