POWER CONNECTIONS
Superterm CIC1800 / CICP1400UL
16
POWER CONNECTIONS
AC Power Source Grounding
The Superterm main circuit board has built-in
surge suppression devices. The surge suppressors
require a good earth ground connection to operate
effectively.
Check the DC resistance between the 120VAC
power ground terminal and a known earth ground
such as a metal water pipe or structural steel
building component
CAUTION
DC resistance between the 120VAC power
ground terminal and a known earth ground
must be no greater than 50 ohms.
If the DC resistance is acceptable, install the
120VAC power cabling using the ground terminal
as the earth ground.
120VAC Power
The Superterm system requires 120VAC, 60 Hz
voltage. The incoming 120VAC source voltage
connects to the AC Input Power Terminal Block
located in the lower left-hand corner of the
Superterm cabinet (see Figure 7).
NOTE:
Use of a dedicated, unswitched
120VAC power source results in optimal
performance with minimum interference.
Superterm units with optional
220VAC
power are
available where required for use outside of North
America. This feature not evaluated by ETL.
WARNING
Verify that the AC source voltage is switched off
at the breaker panel before proceeding with
connections.
Table I lists the incoming 120VAC source voltage
connections to the AC Input Power Terminal
Block.
Table 1- AC Input Power Terminal Block Connections
Incoming 120VAC Wire Color AC Input Terminal Block
Line Black
L
Neutral
Ground
White
Green
Figure 7 - AC Input Power Terminal Block
Содержание SUPERTERM CIC1800
Страница 27: ...Figure 15 Superterm Circuit Board Relay Location...
Страница 29: ...RELAY CONNECTIONS Superterm CIC1800 CICP1400UL 29 Figure 16 LOCAL and REMOTE Power Configurations...
Страница 53: ...Figure 34 COM1 Terminal Strip Connection...
Страница 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Страница 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Страница 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Страница 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Страница 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Страница 73: ...SETTINGS Superterm CIC1800 CICP1400UL 73 Figure 46 232 1 EOL1 and EOL2 Jumper Locations and Settings...
Страница 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Страница 77: ...Figure 48 Jumper Locations and Settings...
Страница 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Страница 83: ...Figure 53 256K Memory Upgrade Installation...
Страница 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...