POWER CONNECTIONS
Superterm CIC1800 / CICP1400UL
18
Step-Down Transformer Connection
The Superterm circuit board is powered from an
internal power supply driven by a separate step-
down transformer. The step-down transformer is
mounted on the bottom ledge of the Superterm
cabinet (see Figure 2, page 5, Superterm
Components).
The Step-Down transformer connects to the
Superterm circuit board through the Power Input
terminal strip (see Figure 8, page 11, Superterm
Circuit Board Layout).
Table 2 lists the connections between the Step-
Down Transformer and the Superterm Power Input
terminal strip. Refer to Figure 9, page 13, while
reading Table 2 for Step Down Transformer to
Superterm Circuit Board connections.
NOTES: If the Superterm is NOT using the
optional Expansion Power Supply, leave the
female Molex connector from the transformer
unconnected.
If the Superterm is equipped with an Expansion
Power Supply, connect the female Molex
connector from the Expansion Power Supply to the
male Molex connector of the Transformer
Assembly (see Figure 9).
Power Input Terminal Strip Jumpers
Pins 1, 2, and 3 of the standard Superterm (with no
Expansion Power Supply) must be jumped
together. Table 3 lists the pin connections on the
Power Input terminal strip that require jumpers.
Refer to Figure 9, page 13 while reading Table 3
for Power Input terminal strip jumper connection.
NOTE: If using an Expansion Power Supply, pin 1
must be open, and pins 2 and 3 must be jumpered
together. Refer to CAUTION on page 13.
Battery Backup Connection
During power interruptions, the Superterm
continues operating for a maximum of 4 hours via
an on-board 7A-hour back-up battery (standard
version) or a 12A-hour back-up battery (expanded
version).
Table 4 lists the connections from the Battery
Backup to the Superterm Power Input terminal
strip. Refer to Figure 9, page 13, while reading
Table 3 for Battery Backup to Superterm Circuit
Board connections.
WARNING
Do NOT connect the Backup Battery or provide
AC source voltage to the Superterm until all
accessory cabling is completed.
Table 2 - Connection Table for Step-Down
Transformer
Power Input Terminal Strip Transformer
Assembly
Pin #
Function
Wire Color
Function
1 REG
IN
2 DC
3 CHARGER
4 +12V
5 -BAT
6 +BAT
7 AC2
Black
AC
Power
8 GND
Yellow
GND
9 AC1
White
AC
Power
Table 3 - Connection Table for Terminal Strip
Power Input Terminal Strip Backup
Battery
Pin #
Function
Jumper
1
REG IN
Jump to Pin 2 (DC)
2
DC
Jump to Pin 1
(REG
IN) &3 (CHARGER)
3
CHARGER
Jump to Pin 2 (DC)
4 +12V
5 -BAT
6 +BAT
7 AC2
8 GND
9 AC1
Table 4 - Connection Table for Backup Battery
Power Input Terminal Strip Backup
Battery
Pin #
Function
Function
1 REG
IN
2 DC
3 CHARGER
4 +12V
5
-BAT
Neg (-) post
6 +BAT
7 AC2
Pos
(+)
post
8 GND
9 AC1
Содержание SUPERTERM CIC1800
Страница 27: ...Figure 15 Superterm Circuit Board Relay Location...
Страница 29: ...RELAY CONNECTIONS Superterm CIC1800 CICP1400UL 29 Figure 16 LOCAL and REMOTE Power Configurations...
Страница 53: ...Figure 34 COM1 Terminal Strip Connection...
Страница 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Страница 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Страница 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Страница 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Страница 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Страница 73: ...SETTINGS Superterm CIC1800 CICP1400UL 73 Figure 46 232 1 EOL1 and EOL2 Jumper Locations and Settings...
Страница 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Страница 77: ...Figure 48 Jumper Locations and Settings...
Страница 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Страница 83: ...Figure 53 256K Memory Upgrade Installation...
Страница 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...