DOOR CONNECTIONS
Superterm CIC1800 / CICP1400UL
24
Door Status Sensor Connection
Door Status sensors connect to the Superterm
through eight terminal strips labeled DR 1 through
DR8 (see Figure 13).
Table 12 lists the connections between the DR1
through DR8 terminal strips and the Door Status
sensor.
Table 12 - Connection Table for Door Status
Sensor
DRx Terminal
Strip
Signal Door
Status
Pin #
Sensor Function
15 Alarm
Positive
16 Return
Negative
NOTES:
Refer to page 32, Alarm Connection, to
configure Door Status sensors as supervised
alarms.
Door Status sensor connections to the Superterm
are not sensitive to polarity.
Door Status Sensor Cable Requirements
Door Status sensors require a 22AWG, 2-
conductor, stranded, shielded, cable with drain wire
between the Superterm and the particular unit (see
Figure 13).
NOTE:
DO NOT use twisted pair cables.
Table 13 lists the cable gauge-vs-length
requirements for proper operation of the Superterm
and the Door Status sensor.
Table 13 - Cable Requirements for Door Status
Sensor
Unit Distance
Wire
Gauge
Door
Status
1000ft/305m 22AWG
Shielded
w/drain
Sensor
CAUTION
Keep all drain and cable shield wires between
the Superterm and Keypads short. Connect
drain and cable shield wires to the ground posts
located on both sides of Superterm cabinet. DO
NOT ground drain wires and cable shields at
any other point.
Figure 13 - Door Status Sensor to Superterm Connections
Содержание SUPERTERM CIC1800
Страница 27: ...Figure 15 Superterm Circuit Board Relay Location...
Страница 29: ...RELAY CONNECTIONS Superterm CIC1800 CICP1400UL 29 Figure 16 LOCAL and REMOTE Power Configurations...
Страница 53: ...Figure 34 COM1 Terminal Strip Connection...
Страница 55: ...Figure 35 Connecting Auxiliary RS 232 and RS 485 Devices to the Superterm...
Страница 57: ...Figure 36 Expansion Input Output Board Layout in Superterm Cabinet...
Страница 63: ...Figure 41 DI DO Board Layout Figure 42 DI DO Board to Superterm Power Connection...
Страница 65: ...Figure 43 DI DO Board Alarm Input Terminal Strip...
Страница 67: ...Figure 45 DI DO Board Relay Output Connections and Address Setting...
Страница 73: ...SETTINGS Superterm CIC1800 CICP1400UL 73 Figure 46 232 1 EOL1 and EOL2 Jumper Locations and Settings...
Страница 75: ...Figure 47 COM1 COM2 and MONITOR Jumper Locations and Settings...
Страница 77: ...Figure 48 Jumper Locations and Settings...
Страница 79: ...SETTINGS Superterm CIC1800 CICP1400UL 79 Figure 49 Superterm Door Strike Jumper Settings...
Страница 83: ...Figure 53 256K Memory Upgrade Installation...
Страница 85: ...UPGRADING Superterm CIC1800 CICP1400UL 85 Figure 55 2MB Expansion Board Installation...