Operation Manual
Track Supply 6 kW
80 / 125 A at 400 / 480 V
BAL9100-0124c-EN
www.conductix.com
Page 11 of 44
6.3
Environmental data
•
Ambient temperature
+5°C to +40°C, power de-rating 3% / °C between 40°C and 55°C
•
Humidity
< 90% non-condensing
•
Ambient air
No salt water, no conductive dry or wet dust! (e.g.
carbon fibers). Avoid extreme environment conditions
(e.g. very dusty, Oily and/or chemical influences)!
•
Altitude de-rating
1% of power / 100 m above 1000 m, up to a max. of
3000 m above sea level
•
IP classification
IP 20 (limited by exhaust vents on top and other ventilation openings)
•
Pollution Degree
PD = 2. Non conducting pollution present, that may become temporarily conducting if
moisture is present after switching off.
•
Storage temperature
-20°C to +60°C
•
Transport temperature
-20°C to +70°C
•
Maximum Vibration
3 mm at 2 - 9 Hz, max. acceleration 0,5 g at 9 - 200 Hz
•
Maximum operating shock
8 g, 11 ms
•
Maximum shipping shock
15 g, 11 ms in packaging / transport box
The Track Supply requires for correct cooling a sufficient air flow.
Ensure free air flow at all times and if Track Supply is mounted in a
cabinet inspect filters for dust and oil blockage regularly.
Shielded control cables are not strictly required but to improve the
EMC are recommended.
In order to avoid induced voltages at 20 kHz, the control cables and
other cables should not be run close to the IPT
®
track cable and
especially not over distances > 5 m. Shielded twisted pair cable will
help reduce the capacitive coupling effect. The shield should be
grounded at one end only.
•
Space around cabinet
Sufficient air flow has to be guaranteed!
Recommended clearances:
200 mm over the Track Supply
200 mm in front of the Track Supply
100 mm sides of the Track Supply
Air in
Air out