6
Technical data
6.1
Electrical data - specifications
6.1.1
Electrical output data – specifications for 400 V and 480 V versions
•
Continuous output power
6 kW
•
Overload capability
137% (8 kW) for max. 1 minute / 10 minute at 40°C,
with average load derating to 4.9kW
•
Output current
80 A or 125 A
±
2A @ 20 kHz
±
50 Hz
•
Optimal load track inductance
58
µ
H +2
µ
H for 80 A Track Supplies
26
µ
H +2
µ
H for 125 A Track Supplies
•
Nominal output voltage range
560 - 665 V rms (80 A), 380 - 475 V rms (125 A). Overloads will increase the voltage.
•
Impedance output to PE
180 Ohm (center capacitively referenced)
•
Connection to primary cable
Stainless Steel M8 bolts for 35 mm² and 20 mm² HF Litz cables. Torque range 9-10 Nm.
6.1.2
Electrical input data – specifications for 400 V versions
•
Input nominal supply voltage
400 V / 50 Hz, 3-phase symmetric, neutral grounded
•
Supply voltage tolerance
-10% to + 10%, with proportional cont. power de-rating for input
voltages other than nominal value
•
Efficiency at rated load
94%
•
Power factor (cos
ϕ
)
0.78
•
Supply current
12 A at rated power / voltage
•
Input connector
Supplied HAN-6HSB in Han-16B connector with PG 21 or M25
cable gland. Maximum outside cable diameter is 18 mm. Use
flexible cable 6 mm
2
.
•
Input leakage current
16 mA rms in standby. Occasional 200 mA peak pulses for 250 µsec
at rated load. Ground leakage equipment must be rated accordingly if
used.
•
Internal fuses
16 A gS or gRL. Semiconductor and wiring protection.
•
Harmonic currents (rated load)
5th -4.5dB, 7th -9dB, 11th -21.6dB, 13th -21.7dB (on fundamental)