Operation Manual
Track Supply 6 kW
80 / 125 A at 400 / 480 V
BAL9100-0124c-EN
www.conductix.com
Page 21 of 44
E026
Track Supply output open circuited
•
Track not connected
•
Track cable damaged or cut
E027
DC bus voltage high
•
Mains overvoltage, e.g. lightning or other disturbance
E028
DC bus voltage low
•
Phase of mains supply missing, e.g. fuse blown
•
Weak mains supply
E029
Internal current software limit
•
High peak load
•
Track is open circuited
•
Track is detuned
E030
DC bus voltage unstable
•
At power up no stable DC bus voltage could be detected due to
a mains supply disturbance
E031
Inductance high
•
Track tuning capacitor aging, failure or loose connection inside
capacitor box
•
Incorrect commissioning
•
Pickups added after commissioning
•
Track/ Feeds repositioned or lengthened after commissioning
E032
Inductance low
•
Track tuning capacitor aging, failure or loose connection inside
capacitor box
•
Incorrect commissioning
•
Pickups added after commissioning
•
Track/ Feeds repositioned or lengthened after commissioning
E033
3.3 V on board power supply failure
•
Communication power supply overload/failure
E034
3.3 V on board power supply failure
•
Micro power supply overload/failure
E035
3.3 V on board power supply failure
•
Analog power supply overload/failure
E036
3.3 V on board power supply failure
•
FPGA power supply overload/failure
E037
5 V on board power supply failure
•
5 V power supply overload/failure
E038
24 V control board supply failure
•
24 V power supply overload/failure
•
24 V on external Han 10 being used inappropriately
E039
FPGA configuration error
•
FPGA failure
•
Flash memory failure
•
SPI bus problem
E040
FPGA SPI bus error
•
SPI bus problem
E041
Invalid output voltage measurement
•
FPGA failure
E042
Invalid output current measurement
•
FPGA failure
E043
Invalid internal current measurement
•
FPGA failure
E044
Oscillator error
•
Micro oscillator failure
E045
FPGA software error
•
Software not compatible
E046
Zone controller 1 error
•
Zone controller fault report (external)
E047
Zone controller 2 error
•
Zone controller fault report (external)
E048
DIP switcher
•
Wrong DIP-switch setting
E049
Output peak power high
•
See E022; to many loads on the track or power demand to
high