4.3.3 Status Page
The following screens will be seen on the microprocessor display of the
HE2 MC3
during normal operation.
The display will default to the status page.
The first line shows if the
HE2
is ON or OFF.
The second line shows the relative humidity and the temperature of the area
under control. If an external control signal is used to control the
HE2
, the
second line will show the signal value in percentage or it will be blank if ON/
OFF mode has been selected.
The third line will show information about the system operation such as:
•
Purge in Progress
•
High Temp Reduction
•
Assisted Drain
•
Pump Delay
•
Manual Drain
•
Dilution Cycle
•
Panel Switched Off
•
Drain Cycle
•
H2O Temp Reduction
•
Filling...
•
External Enable
•
Max Run Drain
•
Out of Occupancy
•
No Demand
The fourth line will show the Setpoint or any of the following alarms:
•
Leak Detected
•
High Water Level
•
Safety Interlock
•
H2O Temp Fault
•
Pump Fault
•
Service PureFlo
•
Disinfection Due
•
PureFlo Due in *** d
•
Service Due
•
Disinfect in *** d
•
Drain Fault
•
Service Due in *** d
•
Water Inlet Alarm
4.3.4 Information Pages
From the Status Page, pressing the down arrow key will display the informa-
tion pages.
The first information page displays the current Date, Time and Day.
If stage control is enabled, the second page will display the status of the
Stages. “0” will show the stages that are closed, and “1” shows stages
which are open. If stage control is disabled, N/A is displayed.
The third information page will display the H2O Temperature. N/A will be dis-
played if the H2O option is not installed, or if the pump is not running.
Whenever the pump is running, the water temperature sensor will monitor
the water temperature. If at any point the water temperature remains above
the limit for 10 seconds, a Temperature Reduction Cycle would initiate.
If the water temperature does not drop below the setpoint after the “Fault
Time” the controller will enter a Water Temperature Fault (see “Fault Modes’).
The next information page is the Dilution Cycle. This page will display the
Interval, and how many minutes until the next Dilution Cycle is due.
Pressing the down arrow will navigate to the fifth information page. The sec-
ond line will display the Drain Cycle Mode, i.e. Interval or Time mode. The
fourth line will display how many minutes until the next Drain Cycle is due.
HE2 ON
55 % rH @ 21 C
Setpoint: 60 % rH
HE2 ON
55 % rH @ 21 C
Filling
Setpoint: 60 % rH
HE2 ON
55 % rH @ 21 C
Filling
Setpoint: 60 % rH
H2O TEMPERATURE
Actual: 10 C
Limit: 20 C
DATE TIME AND DAY
YY:MM:DD
01:01:11
HH:MM
12:00
Monday
STAGE CONTROL STATUS
S2 S3 S4 S5 S6 S7
1 1 1 1 1 1
DILUTION CYCLE
Interval:
___
400
_
mins
Due in:
_____
200
_
mins
DRAIN CYCLE
Interval Mode
Interval:
____
12
__
hrs
Due in:
_____
200
_
mins