Commissioning (
OEM Circulating
and
OEM Direct Feed
)
1. Validate temperature and air flow.
Measure the air volumes and the air conditions, check this against the
design data.
2. Adjust the water level (Circulating ONLY).
If the water level is incorrect, adjust the float on the water inlet
valve to ensure that the water level in the tank is correct. See below.
Increase water depth
Decrease water depth
Torbeck inlet
valve
Water Level
How to adjust the water inlet valve
3. Water Conductivity.
Measure the TDS of the water in the tank. Use the manual as a guide to the accept-
ability of water quality.