23
3.1.7 Step 6 - Connect Power Supply to Management System.
Warning: All work concerned with electrical installation MUST only be performed by skilled
and qualified technical personnel. (e.g. electrician or technicians with appropriate training).
The customer MUST be responsible for ensuring their suitability.
Please observe the local regulations concerning the provision of electrical installations
.
Electrical Connections
An electrical power isolator (not supplied) must be fitted within 1m (39”) of the
HE2
Management System. This
is essential for the purposes of maintenance and emergencies.
Step 6
Power
Terminals
<1m (39”)
Terminals E, L and N
230Vac / 5A fused power supply - Europe
110Vac / 10A fused power supply - US
The power supply should be connected to
the E, L and N terminals as shown.
Model shown
HE2 MC3
The electrical power cable to
HE2
Management System should be suitably
rated for a 230V / 5 Amp in the EU or
110V / 10 Amp load in the US. Refer to
label on
HE2
MC3
Management System.
Power
Earth
Live
Neutral
E
L
N
E
L
N
Incoming
Power Supply
EU 230V / 5A
US 110V / 10A