Step 10 - PureFlo Cartridge
Screen ten allows setting the PureFlo cartridge replacement interval counter
parameters for the HE2 system. The HE2 system will provide a warning when
PureFlo Ag+ Cartridge replacement will soon be required, and will activate an
alarm output when the replacement frequency is reached. The PureFlo Ag+
cartridge replacement counter does not interrupt normal system operation.
After replacing the PureFlo Ag+ Cartridge, pressing and holding the right
arrow button for ~10secs will reset the “Due In” counter and clear a fault if
applicable.
Step 11 - Date, Time and Day
The date, time and day are preset in the HE2 system and backed up with a
battery. The system will also automatically adjust for daytime saving. However,
screen eleven allows the date, time or day to be adjusted if required. If incor-
rect, “Occupancy Mode” will not operate as required.
Step 12 - Set Occupancy
The occupancy function can be used to control the hours during which the
HE2
operates. Select periods of occupancy from the following list:
Always On, Every Day, Weekdays or Weekends. Default value is Always On.
When a mode is selected, use the right arrow to specify the switch on/off
times. Default values are shown.
Step 13 - Restore Default
To restore all default values select Yes.
When selecting Yes, all programming values will be reset to default value as
they were when the unit left the factory.
PUREFLO CARTRIDGE
Interval:
____
3
_
mths
Replace in:
__
90
_
days
DATE TIME AND DAY
YY:MM:DD
___
11:03:28
HH:MM
______ ___
12:15
___________ __
Friday
OCCUPANCY
<-
_
Switch on:
__
09:00
___
Switch off:
_
17:00
OCCUPANCY
<-
_
Switch on:
__
09:00
___
Switch off:
_
17:00
OCCUPANCY
Mode: Everyday ->
RESTORE DEFAULTS
No