5.2
HE2 MC3
& OEM Maintenance Guide
Please note that the information given below is only to act as a guide and the frequency of maintenance may
depend upon the unit’s age, usage and water quality.
Correct maintenance is vital to ensure optimum output and reliability.
All humidifiers will form part or your hot and cold water system and as such require you to undertake certain
duties with regards to “The control of Legionella microbes in water systems” (L8). Your water sampling / testing
and disinfection regime must be based on details in the O&M manual and from results of a site specific risk
assessment. For this type of Evaporative Humidifier,
Condair Ltd.
recommend that disinfection is undertaken
at least twice a year.
If any further assistance is required or you are interested in a planned maintenance quote, please contact
your
Condair distributor
.
Operations
Minor Service
Main Service
Replace inlet water filter
Yes
Yes
Check PureFlo & service if applicable
Yes
Yes
Clean inlet valve strainer
Yes
Check water inlet solenoid valve operation
Yes
Yes
Clean water inlet solenoid valve strainer
Yes
Yes
Check pump operation
Yes
Yes
Check all hoses
Yes
Yes
Check water distribution header pipes
Yes
Yes
Clean water distribution header pipes
Yes
Check drain valve operation
Yes
Yes
Clean drain valve
Yes
Clean pump basket filter
Yes
Yes
Clean stage option solenoid valve kits (if applicable)
Yes
Scrub clean front section of tank
Yes
Yes
Remove matrix cassettes and scrub clean all sections of tank
Yes
Disinfect system at 6 monthly intervals
Yes
Replace all feed hoses where necessary
Yes
Replace flow restrictors
Yes
Check all matrices for full saturation during operation
Yes
Yes
Measure spray header flow rates
Yes
Test control and high water level float switch
Yes
Check and secure all electrical connections
Yes
Yes
Check overall installation for leaks and damage
Yes
Yes
Check inlet float valve water level setting
Yes
Yes
Check software settings
Yes
Yes
Test cleaning and flush cycle operation
Yes
Reset maintenance intervals
Yes
Yes
Test operation of humidistat and controller (if applicable)
Yes
Yes
Test safety interlock and controls operation
Yes
Clean unit throughout
Yes
Yes
Check air velocities at face of the matrix
Yes
Check any fitted options
Yes
Yes
Update service log book
Yes
Yes
Add DISIFIN disinfection tablet to reservoir, monthly or as required
Yes
Yes