3.1.9 Step 8 - Connect
HE2
Controls
HE2 MC3
Warning:
The
HE2 MC3
Panel and Evaporative Module contain live mains voltage and be isolated before com-
mencing installation and maintenance work.
Step 8 Controls
Terminals
Controls Wiring
Interlocks are connected to terminals 12-15 and provide a method of
switching the unit on or off, or overriding the normal operation of the
HE2
.
The interlocks are supplied pre-wired with a link as standard.
Thermostat/Humidistat Wiring:
When a stat is used, it should be wired to terminals 12 & 13.
If a control stat (N/C) and high-limit stat (N/C) are required, they would
be wired in series onto 12 & 13 and the unit will switch off in the event
that either contact is open.
Safety Interlock:
If fault indication is required on the microprocessor, for example where
the connection is an interlock for a water treatment product such as an
Ultra-Violet (UV) Steriliser, terminals 14 & 15 should be used. If the
contact is opened, the unit will not operate and a fault will be indicated.
Sensor / External Signal:
Terminals 16-19 are used to power a sensor and provide the
HE2 MC3
with temperature and humidity readings. If an external signal (i.e. from
a BMS) is to be used, it should be wired onto terminals 17 & 18 as
shown.
Common Fault Contact:
Terminals 20-22 are used to provide a common fault output, e.g. to
indicate to a BMS system that there is a fault preventing the system
from operating correctly. A Normally Open (N/O) contact, i.e. one
which will close in the event of a fault, or Normally Closed (N/C) con-
tact, i.e. one which will open in the event of a fault, is available as
required by wiring to the appropriate terminals. The
HE2 MC3
control
panel has the following fault modes: Safety Interlock Open, Water Inlet
Alarm, High Water Level, Service Due and PureFlo Ag+ Cartridge
Replacement Due. An explanation of each fault mode can be found in
the “
HE2
- Alarms and Fault Modes” section of this manual.
Controls
+ 24 Vdc
External Enable
+ 24 Vdc
Safety Interlock
+ 24 Vdc
0 Vdc
Analogue
Input /
rH
Analogue
Input /
Temp
Common Fault C
Common Fault N/C
Common Fault N/O
12 13 14 15 16 17 18 19 20 21 22
+
–
rH
T
C N/C N/O
Factory
supplied
with a link
Factory
supplied
with a link
Connected to
Humidity and
Temperature Sensor
Volt Free
Contact
Common Fault
or...
or...
12 13
16 17 18 19
+
–
Control
Signal
0-10 Vdc
2-10 Vdc
4-20 mA
Humidistat
(N/C)