44
7. Drain Duration.
Once the water level is correct, switch the panel to manual drain, and time how long it
takes for the tank to empty whilst in normal operating conditions (i.e. the fan on). Make a note of the time
taken; this will become the “DRAIN DURATION” in the commissioning section of the software.
8. Inlet Duration.
Once the tank has fullly drained, allow the tank to refill. Time how long it takes to fill until
the low level float switches. This will give you the “Inlet Fault Delay”.
System Code:
Operating Capacity (ltrs)
MAX Inlet Duration (mins)
HE2
-X1X
16
3
HE2
-X2X
25
4
HE2
-X3X
33
5
HE2
-X4X
41
6
HE2
-X5X
49
7
HE2
-X6X
57
9
HE2
-X7X
66
10
HE2
-X8X
74
11
HE2
-X9X
82
12
HE2
-X1X
88
13
HE2
-X2X
96
14
HE2
-X3X
104
15
This table should be used as a guide only. Ensure you correctly time how long it takes for the tank
to fill.
9. Pump Delay.
Adjust the pump delay using the table in the manual if necessary. This will be entered as the
“PUMP DELAY” in the commissioning section of the software.
10. Water Conductivity.
Measure the TDS of the water in the tank. Use the water quality guide in this manu-
al as a guide to the acceptability of water quality.
11. Enter the commissioning section of the software.
Enter the commissioning code into the software, and
input the appropriate values using the data collected from the instructions in this section of the manual. It
will also be necessary to input the temperature unit (default °C), and the air temperature (minimum and
maximum) range for the sensor.
12. Matrix Wash over Cycle.
The matrix wash over cycle is designed to flush new matrix material to remove
any dust and glue left after the manufacturing of matrix material. Whilst in the commissioning section of the
software, refer to the manual for the “MATRIX WASH OVER DURATION”. Select “yes” to start the cycle.
13. Enter the programming section of the software.
Whilst the “MATRIX WASH OVER” is underway, enter
the programming section of the software. Input the “
HE2
CONTROL” and “STAGE CONTROL” settings,
depending on the requirements.