5
WARNING: The
HE2
must be installed, operated and maintained in accordance with this
manual. Failure to do so could result in contamination that might cause Legionnaires” dis-
ease, which can be fatal
.
1.4
Correct Use
The
HE2
system is intended for adiabatic humidification and cooling. Any other, or further, application is not
considered use for the intended purpose.
Condair Ltd.
cannot be made liable for any damage or injury attribut-
able to inattentive, inappropriate, negligent or incorrect operation of the equipment whether or not caused
deliberately.
Caution:
To prevent water stagnation and microbial contamination, the
HE2
power supply should be
left switched on continuously. If the system is switched off for prolonged periods, typically longer than
one week (subject to risk assessment) the pipework and system should be disinfected as per instruc-
tions and a full risk assessment undertaken to ensure safe operation.
1.5 Warranty
HE2
parts are warranteed for 2 years from invoice date with the exception of replacement items listed in the
routine maintenance section. Failure to observe the manufacturers installation and maintenance recommenda-
tions and instructions will invalidate the warranty.
Condair Ltd.
cannot be made liable for damage or injury
attributable to failure to observe the manufacturers installation and maintenance recommendations and
instructions.
1.6 HE2
OEM Versions
The
HE2
OEM versions are designed for customers who are familiar with evaporative humidification/cooling
systems and wish to provide their own controls and hygiene precautions. OEM versions are designed to be
components in a hygienic humidification/evaporative cooling system, and are not to be considered as entire
systems in their own right. There are a number of requirements that the customer
MUST
ensure are met in
order to bring the OEM versions up to a standard to comply with VDI hygiene specifications. These are listed
in this manual.
Warning: The
HE2
“OEM” versions, unlike the
HE2 MC3
, do NOT incorporate, as standard,
methods to control the growth of micro-organisms (including the bacterium which causes
Legionnaire’s disease). When designing or installing an air handling system that incorporates
an “
OEM HE2
”, appropriate micro-organisms and microbial control methods MUST be consid-
ered and this should only be undertaken by suitably qualified persons. A risk assessment
MUST also be undertaken in relation to control of micro-organisms and microbial growth,
especially Legionnaires disease. If in doubt and for further information, contact
Cond air AG
.