3.1.5 Step 4 - Install Drain Pipework
The Evaporative Module features a gravity drain and overflow which must be connected to the main building
drain with 28mm copper or stainless pipework. The normally open drain assembly can be reversed to face in
the opposite direction to suit either left or right feed pipe-work. This drain assembly should be connected to
the main building drain via the 28mm push fit connection (with an appropriate fall for gravity drain) and must
be trapped to a suitable depth in accordance with the operating pressure of the AHU.
Please note:
HE2 XL
Systems do not have a combined drain and overflow. The system is supplied with drain
plumbing and a separate 32mm push fit elbow on the overflow. They should NOT be combined to ensure
adequate flow rate.
Motorised
Drain Valve
Integrated Overflow
(
HE2
MC3
XL systems
have a separate drain
and overflow)
28mm Drain Plumbing
(Not supplied)
Drain Trap Assembly (Not supplied)
Drain Trap Sizing: Allow a depth of 25 mm (1”) for every
250 Pa (1”Wg) of duct pressure (eg 1000 mm (4”) for
1000 Pa (4”Wg) duct pressure).
28mm Push Fit
Tee
For negative pressure AHU systems
drain must be isolated. DO NOT
common with AHU drains as back-
flow into humidifier may occur.
When installing the drain,
please allow an adequate
fall for gravity drain.
NOTE:
The drain connection
must be made via an air gap.