22
3.1.6 Step 5 - Position the Management System
The Management System should ideally be positioned as close to the Evaporative Module as possible for
ease of servicing and maintenance. The management system is IP31 rated. Do not mount control panel where
exposure to weather or moisture is possible.
The Evaporative Module is supplied with one 10m (33’) 12-core electrical inter-connecting cable for connection
to the Management System (See Stage 5 Electrical Installation for details). The
HE2
MC3 Plus
management
system has two 12-core electrical inter-connecting cables.
If it is necessary to extend this cable ensure it is no longer than 100 meters (328’) and rated for 110V / 10A or
230V / 5A according to the rating shown on the CE label.
The
HE2
Management System must have an electrical power isolator (not supplied) fitted within 1m (39”) for
purposes of maintenance and emergencies.
Electrical Power
Isolator (Not supplied)
Management System
Inter-connecting 12 core cable(s)
between Evaporative Module and
Management System. (Supplied
pre-wired to Evaporative Module)
Caution: Ambient Conditions:
Temperature
5-45°C
Humidity
<85% rH
NB: Ensure that the
HE2
Management system is
accessible for maintenance.
Fixing Part 1
Fixing Part 2
Minimum Clearance dimensions
250mm
(10”)
100mm
(4”)
100mm
(4”)
420mm (17”)
100mm
(4”)
HE2 MC3 Plus
360mm (14”)
HE2 MC3
300mm (12”)