41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
47
7.6.5 Delay Т1
In this submenu the installer sets the time to Delay T1. T1 is the time delay needed for reaction of the security
personnel on the protected site. T1 provides a time delay for the personnel to go to the zone in fire alarm and to check
the situation. The operation of time delays T1 and T2 are described with the algorithm below.
To access the DELAY T1 submenu, enter in the installer’s menu - 6. GENERAL SETTING - 6.5) DELAY T1. The
screen displays:
Use the up and down arrows to set the delay T1. The time interval is
in range 0 - 60 sec.
Confirm the settings with ‘ENTER’ button.
7.6.6 Sounders Mode
In this submenu the installer sets the sounders operation mode.
To access the SOUNDERS MODE submenu, enter in the installer’s menu - 6. GENERAL SETTING - 6.6) SOUNDERS
MODE. The screen displays:
Use the functional buttons to set:
(1) ALARM TONE*
– Set the alarm type sound. Enter the submenu
and use the up/ down arrow buttons to select a number from 1 to 32
for the alarm sound – the reference parameters for the selected
sound are listed on the last row of the screen.
(2) EVACUATE TONE*
– Set the evacuation type sound. Enter the
submenu and use the up/ down arrow buttons to select a number
from 1 to 32 for the evacuation sound – the reference parameters for the selected sound are listed on the last row of
the screen.
* Note:
The main tone type for sounders is 27 with main sound frequency 2500Hz.
(3) EVACUATE SETTINGS
– The menu button is active only in ZONAL operation mode. Press it to make the following
evacuation settings for sounders operation.
The EVACUATION TIMEOUT is a time delay introduced and running until starting evacuation of the site. Enter the
submenu and use the up/ down arrow buttons to set the EVACUATION TIMEOUT delay from 0 to 10 minutes. In a fire
situation only the sounder of the zone(s) with alarm condition will be activated.
After the set evacuation timeout delay is over the sounders in the whole site are activated also, according the settings
of the (4) MODE button in this menu:
Use the (4) MODE button to set the action of the sounders:
-
SND/FLASH
– The addressable sounders are activated with sound and LED indication. The sounder outputs
on the panel PCB are activated also.
-
SND
– The addressable sounders are activated with sound indication only. The sounder outputs on the panel
PCB are activated also.
-
FLASH
- The addressable sounders are activated with LED indication only. The sounder outputs on the panel
PCB are not activated.
Use the (2) EVAC.CYCLE button to set a cycle sounding of the sounders in evacuation mode. The function requires
setting of two special times defining time intervals for sounders operation as follows: