41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
49
7.9. Software Revision
In this menu the installer can review the software versions of the
main board and used loop modules and also has possibility for
firmware update of the main processor unit. The screen displays:
7.10. Network
(supported for Soft. Revision 2.8 and higher)
In this menu the installer can make the settings for the redundant network between fire panels.
7.10.1 Network Settings
To access the NETWORK settings, enter in the installer’s menu - 10. NETWORK – 10.1) SETTINGS. The screen
displays:
In this submenu the installer
enters a number, name and sets the status of the panel in the redundant network. Use the
up/ down arrow buttons to set the panel number. Move on the second row with right arrow button and enter a specific
name up to 40 symbols, including intervals.
(1) – REDUNDANCY
- Use the button to set an option for ignoring a fault message for broken connection in the
redundant network. Set OFF if you do not want to monitor the status of the connection in the redundant network; set
ON if you want to monitor the continuity of the redundant network.
(4) – CHANGE -
Use the button to set the status of the panel in the redundant network - ENABLED (the panel is
enabled for operation in the network) / DISABLED (the panel is disabled for operation in the network). When the panel
is DISABLED from the network it will not receive messages from other panels and will be visualized as FAULT.
Confirm the setting with ‘ENTER’ button. You can also escape from this menu with ‘CANCEL’ button.
7.10.2 Panels Settings
To access the PANELS settings, enter in the installer’s menu - 10. NETWORK – 10.2) PANELS.
On the screen are listed the panels with their current state in the
redundant network:
•
NEW
– The panel is new in the system. To save it press
button (3) SAVE.
•
NORMAL
– The redundant network for the panel is enabled.
•
THIS
– The panel from which the redundant network is
reviewed.
•
FAULT
– The panel is DISABLED or there is problem with the redundant network.
•
NONE
– No panel connected to the redundant network.
All new panels connected to the redundant network can be saved with (3) SAVE button. The panels with current state
NORMAL, THIS and FAULT can be deleted from the network with (3) REMOVE button.
If a new panel enabled in the network is with number already set for another panel the “GENERAL FAULT” LED will
lights on and a message for fault event “Double Panel number” is generated. The installer should change the doubled
panel number for proper operation in the redundant network.
For every panel the installer can set individually the panel’s activity to Receive/ Send messages and/ or commands.
The settings for sending commands can be done only for THIS panel (current panel).
For future use