41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
38
To associate IN 1/ 2 for operation in a group, press button (2) GROUP in the screen of the respective input number. In
the editing field enter the group number using the up/ down arrow buttons.
41IOM040 – Module with 4 inputs
The programming is same for all of the inputs. Use the functional buttons to select an input number.
To program IN 4 you have to press button MORE >>. To see the ID number of the module press MORE >> button
again.
Use the functional buttons to set parameters for the inputs.
For the settings of the IN 1/ 2/ 3/ 4 refer to the submenu of 41IOM010.
To associate IN 1/ 2/ 3/ 4 for operation in a group, press button (2) GROUP in the screen of the respective input
number. In the editing field enter the group number using the up/ down arrow buttons.
41IOM000 – Module potential output
The modules is used for connection of conventional sounders, providing interface connection between a zone with
conventional sounders and 41CPE112 fire alarm panel. Use the functional buttons to set the following specialized
parameters:
(1) OUT 1 –
Set the parameters for the output – see the description of
module 41IOM004.
(1) POLARITY - Use this button to set the type of operation of the
module’s relay. Every pressing of the button changes alternatively the polarity type:
-
NORMAL POLARITY
- The module’s relay will switch on when
receiving of activation signal and will switch off when the signal is
lost.
-
INVERTED POLARITY
- The module’s relay will switch on when
the signal is lost and will switch off when receiving of activation
signal.
Attention:
The event “SOUNDER ON (Zonal)” is used for zonal
activation of the conventional sounders connected to the module.
The output active state during evacuation cycle running is as follows:
Evacuate settings (item 7.6.6) Output state
SOUND/FLASH
ON
SOUND
ON
FLASH
OFF
All set parameters are confirmed with ENTER button. The exit to the main screen of DEVICES SETUP menu is with
pressing CANCEL button.
and
Press