41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
46
7.6.3 Setting Day/ Night Alarm Modes
In this submenu the installer can set the operation alarm mode of the panel.
To access the DAY/ NIGHT submenu, enter in the installer’s menu - 6. GENERAL SETTING - 6.3) DAY/ NIGHT. The
screen displays:
Press the functional button ‘2’ to select the preferred alarm mode:
NIGHT
- Select to set nighttime alarm mode. The devices will operate
only in night alarm mode.
DAY
- Select to set daytime alarm level. The devices will operate
only in day alarm mode.
SCHEDULE
- Select to set operation on a schedule. The devices will
operate on the programmed schedule.
The schedule is set in DAY/ NIGHT SCHEDULE submenu - press
functional button ‘4’.
In DAY/ NIGHT SCHEDULE submenu the installer can define the
day and night time intervals for all days of the week. The current
editing value is blinking.
(1) DAY CHANGE
- Press to change the day of the week. Use the up
and down arrows to set the day and night time intervals for the day.
Use the left and right arrows to switch over the editable fields.
(2) ALL
- Press to set the current set day and night time intervals for
all days of the week.
Confirm all settings with pressing ENTER button.
7.6.4 Panel General Settings
In this submenu the installer can make some adjustments for the
panel performance.
To access the PANEL SETTINGS submenu, enter in the installer’s menu - 6. GENERAL SETTING - 6.4) PANEL
SETTINGS. The screen displays:
(1) LANGUAGE
- Press to set the language. Every
pressing of the button changes the currently used
language for the menus.
(2) + Brightness
- Press to increase the brightness of the
screen back light. The maximum value is 20.
(3) - Brightness
- Press to decrease the brightness of the
screen back light. The minimum value is 0.
(4) MORE>>
- Press to switch to other panel settings.
Confirm all settings with pressing ENTER button.
(1) Earth Fault
- Press to enable/ disable the Earth
Fault indication. When the Earth Fault indication is
enabled you have to set a jumper to Earth Fault
terminals on the control panel PCB.
(2) BATTERY
- Press to enable/ disable the
Accumulator Battery Fault Indication. When the
Accumulator Battery Fault Indication is enabled the
panel will monitor the internal battery resistance Ri. In
normal operation Ri<0.3Ω. If Ri>0.3Ω, the panel will alert
for Battery fault with message in Faults menu ‘Battery
High Resistance’. The installer has to change the
accumulator battery with new.
(3) BUZZER
- Press to enable/ disable the buzzer
signalization.
(4) << BACK
- Press to switch back to previous settings.
Confirm all settings with pressing ENTER button.