41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual  

 

 

31 

The panel will ask if you want to disable the selected device only (button (2) THIS) or all present devices (button (3) 
ALL) at the respective Loop number. The exit is automatic to the main screen DEVICES SETUP, as the disabled 
devices are displayed with status DISABLED. 
For example, if the selected device is connected to Loop 1, when pressing the button (3) ALL, all present devices 
connected to Loop 1 will be disabled in the system configuration. To disable in the system configuration all present 
devices connected to Loop 2, the installer has to select a device in Loop 2 and press button (3) ALL. Quick switching 
between Loop 1 and Loop 2 can be performed with button (1) GO TO. 
 
To enable the device again, select its address and press the active button (4) ENABLE. 

 
Note:

 If at the moment of enabling the device, it is in fire alarm mode (the fire signal was generated earlier, when the 

device was still disabled) the panel will alert for the fire alarm situation immediately! 
 
 

7.3.5 Fixing of Wrong Type Devices 

When a device is replaced physically in the system configuration with other type of device, the panel will change its 
status to TYPE ERROR. The installer can quickly correct that using the (3) FIX button, as the name and the zone 
number will be saved for the new device. 
  

 

 

From the main screen of DEVICES SETUP menu, select the device address with TYPE ERROR status and press (3) 
FIX button. The panel will ask if you want to fix the type of the selected device only (button (2) THIS) or all devices with 
wrong type (button (3) ALL) in the respective Loop number. The exit is automatic to the main screen DEVICES SETUP, 
as the fixed devices are displayed with status NORMAL.

 

 

 

7.3.6 Programming of Device Parameters 

 

Attention: Programming device type parameters is available only from access level 3! 

 
The 41CPE112 fire alarm addressable panel operates with full range of addressable detectors, call points, sounders 
and modules via Comelit communication protocol. According the type of the device, the setting parameters are 
different. Use the descriptions below to set the devices in your system configuration. 
To set parameters of a device go to its address number in the DEVICES SETUP menu (the editable address number is 
blinking) and press ‘ENTER’. 
 

Note:

 You can make the device settings also for NEW and DISABLED devices. 

Some parameters are common for all device types and are set in one and the same way: 

 

 

Association to a zone number.

 The first editable parameter is setting the zone number for this device. Use 

the up and down arrows to set the zone number according your specific system configuration. By default all 
devices are associated to Zone 1. 
 

 

Entering of a specific name.

 The installer can enter a specific name for every device. The name can be up to 

40 digits long and it is entered on the second row. Use the left and right arrows to move the cursor. The 
symbols (small and capital letters and characters) are set with the up and down arrows. Confirm the entered 
name with “ENTER”. See also the APPENDIX B. 

 
Two special buttons are implemented in the setup menus of the addressable devices: 

 

 

Button ON/ OFF TURN

 – Using this button the installer can manually to turn on the LED of a device (or the 

sound for sounders 41SAI000 and 41SAB100) when checking its place of installation or checking for double 
addresses in the system. When setting 

ON 

state, the LED of the device lights on permanently in red (sounders 

41SAI000 and 41SAB100 are activated). After exiting the device setup menu, the button turns automatically 

OFF 

and the device’s LED is off too. 

Note:  Devices 41IOM010, 41SAI000 and 41SAB100 have no LED indication. 

Содержание LogiFire 41CPE112

Страница 1: ...EN TECHNICAL AND PROGRAMMING MANUAL Addressable fire panel art 41CPE112 Passion Technology Design LogiFire 41CPE112...

Страница 2: ...from Computer 16 3 3 2 Firmware Update from USB Drive 17 3 3 3 Copying Image File from the Panel to USB Drive 17 4 FULL HARDWARE RESET 17 5 PROGRAMMING OF 41CPE112 FIRE ALARM PANEL 17 5 1 General Info...

Страница 3: ...faults Menu 48 7 9 Software Revision 49 7 10 Network 49 7 10 1 Network Settings 49 7 10 2 Panels Settings 49 7 11 Active Isolators Menu 50 7 12 Access Level 1 50 APPENDIX 50 APPENDIX B 52 APPENDIX C 5...

Страница 4: ...ws x 40 symbols functional buttons and system status LED indication Separate access level passwords provide access to the functions of the panel The fire alarm panel is designed on module structure as...

Страница 5: ...according the requirements of EN54 2 4 Color Grey RAL 7045 Metal box cabinet for wall mounting 330 430 150 mm 1 2 2 Possible Hardware Configurations Minimal Configuration o Control panel main PCB wit...

Страница 6: ...C Max loading capacity of outputs FIRE FAULT and EXT 300 mA DC Max total loading capacity sum of the four mentioned above 2 0 A DC Programmable relay outputs 15A 24VDC Consumption From the main power...

Страница 7: ...ppliances The temperature must be within 5 and 50 C The fire panel is not waterproof Unpack the panel and observe for visible damages due to bad transport or incorrect storing Figure 1 Choose inlets f...

Страница 8: ...buttons 5 Control and navigation buttons Figure 5 1 Description of system status LED indication LED Indication Description GENERAL FIRE red Lights on permanently in case of fire alarm event fire alarm...

Страница 9: ...ry Changing of value or parameter status 5 Description of control and navigation buttons Button Action Description Silence Buzzer The button is active at access levels 1 2 and 3 The button functionali...

Страница 10: ...ce for mounting of a communication module Art 41ECN000 6 Place for mounting of redundant network module Art 41ECB000 7 Place for accumulator battery 1 12V 18Ah 2 2 3 Description of the main PCB contro...

Страница 11: ...S232 interface connector for heat printer USB UTG Micro USB A B connector for firmware update of the main microprocessor via PC or USB flash drive suitable also for programming via LogiProg software B...

Страница 12: ...total current consumption which must not exceed 0 5A Before connecting the last sounder in the circuit parallel to it must be added resistor 10k Figure 10 Connecting sounders to SND output 2 3 2 Conne...

Страница 13: ...s to the loop controller is shown on Figure 13 The maximum current consumption of the devices in the communication line is Imax 500mA If the consumption exceeds this value an over load protection woul...

Страница 14: ...he charging of the accumulator battery is done at maximum current I 2A and charging voltage U 13 65V 2 6 Connecting a Heat Printer The addressable fire alarm panel 41CPE112 is equipped with RS232 inte...

Страница 15: ...rnet network with other 41CPE112 or Logifire addressable panels up to 64 The network module is mounted under the main PCB and is connected to NET connector Figure 19 The module should be fixed with sc...

Страница 16: ...ance and Installer programming access levels is presented in item 5 3 3 Firmware Update ATTENTION The firmware update of the main microprocessor of fire alarm panel 41CPE112 should be performed by qua...

Страница 17: ...te procedure of the main microprocessor accompanied with short beeps Disconnect the USB cable The panel will reset itself automatically after a successful firmware update 3 3 3 Copying Image File from...

Страница 18: ...enus The factory default setting of the language is in English You can change the language after the initial power up as enter in sequence Press CANCEL enter code 3333 select menu 6 GENERAL SETTINGS m...

Страница 19: ...ddress Changing device address Self addressing Automatic self addressing mode Autoaddressing Automatic mode for addressing devices by ID or isolator Panel outputs Parameter programming for the built i...

Страница 20: ...for every of the alarm events For this select the number of the alarm message using up down arrow buttons the number of the selected event is blinking and press ENTER button On the screen is displaye...

Страница 21: ...o back to ALARMS mode and reviewing the alarm messages To review the DISABLED at active alarms and or faults in the system To exit the review fault events mode press CANCEL button 6 4 Review of Runnin...

Страница 22: ...Note that the additional information is different according the type of the warning event NOTE If the device is an input output module the number of activated input output is displayed after the addre...

Страница 23: ...evacuation alert the user has to press the button Levels 2 and 3 In case there is no fire alarm signal from a detector in a zone To start the sounders for evacuation alert the user has to enter in seq...

Страница 24: ...the installer to review and print the system events recorded in the panel memory log file The capacity of the panel memory log file is 10000 events The installer can clear also all panel s memory or t...

Страница 25: ...ce access level 2 7 1 4 Printing Events Attention To print the system events you have to connect printer to the PRINTER terminal on the main board Check your printer connection before entering this me...

Страница 26: ...in screen of ZONES menu as the number of the zone is blinking Submenu 2 DEV VIEW The submenu shows information about the total number of the devices in the respective zone From the main screen of ZONE...

Страница 27: ...cond row Use the left and right arrows to move the cursor The symbols small and capital letters and characters are set with the up and down arrows Confirm the entered name with ENTER button See also t...

Страница 28: ...anel the events FIRE and PRE ALARM are cleared and LED General Fire light off 7 2 7 Programming Delays 2 2 represents times for individual delay setting for activation of FIRE output and the sounders...

Страница 29: ...cted devices in the system configuration Example for the screen display after entering the menu The screen is divided in the following sections 1 Address of the device 2 Zone number 3 Loop number 4 Sy...

Страница 30: ...ton 1 GO TO Note The panel automatically saves the new devices on the serial address The other types of addressing or changing the current set address are described in item 7 4 7 3 3 Deleting Devices...

Страница 31: ...3 6 Programming of Device Parameters Attention Programming device type parameters is available only from access level 3 The 41CPE112 fire alarm addressable panel operates with full range of addressabl...

Страница 32: ...smoke chamber for DAY and NIGHT alarm mode Use the functional buttons 2 DAY and 3 NIGHT to select the sensitivity level Normal Middle Low High All set sensitivity levels are confirmed with ENTER butt...

Страница 33: ...T Press the button to enter in a new screen for checking of the following current parameters Smoke Shows in percent the current level of smoke in the detector s smoke chamber Pollution Shows in percen...

Страница 34: ...e cases when the number of the connected sounders to the loop is up to 60 Sounders 41SAI000 41SCI000 3 MODE Press to choose the operation mode of the sounder SND Sounder activation only in FIRE mode F...

Страница 35: ...he total consumption of the sounders in the loop must be up to 300mA Note The automatic detectors mounted to bases 41SAB100 are assigned at separate addresses in the control panel To calculate the tot...

Страница 36: ...le s input CLASS CHANGE To use the class change function connect the terminals of a switch with normally open contacts to the module terminals SILENCE ALARM STROBE ON Use to disable the sounders in ca...

Страница 37: ...in case of silence alarm in the system TEST Activation in case of test in the system VOICE CYCLE Activation in case starting EVAC CYCLE ON time and deactivation in case starting EVAC CYCLE OFF time th...

Страница 38: ...of conventional sounders providing interface connection between a zone with conventional sounders and 41CPE112 fire alarm panel Use the functional buttons to set the following specialized parameters 1...

Страница 39: ...e system configuration The devices are directly connected to the panel Loop 1 and or Loop 2 The panel will recognize them and gives automatically addresses according the order of the devices in the li...

Страница 40: ...elf addressing It is suitable when the installer needs to add single devices to the system configuration at free addresses The detectors and sounders must not be mounted to the bases the call points a...

Страница 41: ...self addressing enter in the installer s menu 4 ADDRESSING 4 3 SELF ADDRESSING The panel shows the first free address for every of the loops Now the installer can start mounting detectors and modules...

Страница 42: ...ternatively the ENABLED DISABLED status When the sounder outputs are disabled the LEDs Sounder Output Fault Disable and Disable light on permanently 4 Press to set the time delay operation Every press...

Страница 43: ...on 7 5 4 Fault Output In this submenu the installer can disable enable the fault output activation To access the FAULT submenu enter in the installer s menu 5 PANEL OUTPUTS MORE 4 FAULT 1 The function...

Страница 44: ...ENANCE programming menus The settings are analogical for both levels Use the functional buttons to set access code for 1 Press to change INSTALLER CODE 2 Press to change MAINTENANCE CODE 3 Press to en...

Страница 45: ...IME DATE The screen displays The editable field is blinking Use the up and down arrows to set the date and time Use the left and right arrows to switch over the editable fields IMPORTANT NOTES The pan...

Страница 46: ...th pressing ENTER button 7 6 4 Panel General Settings In this submenu the installer can make some adjustments for the panel performance To access the PANEL SETTINGS submenu enter in the installer s me...

Страница 47: ...rom 1 to 32 for the evacuation sound the reference parameters for the selected sound are listed on the last row of the screen Note The main tone type for sounders is 27 with main sound frequency 2500H...

Страница 48: ...ss to change the sounders operation mode Common All sounders will be activated with no sense of zone to which they are connected Zonal Only the sounder of the zones with alarm condition will be activa...

Страница 49: ...network DISABLED the panel is disabled for operation in the network When the panel is DISABLED from the network it will not receive messages from other panels and will be visualized as FAULT Confirm...

Страница 50: ...gs 7 11 Active Isolators Menu This is an information menu for reviewing the active isolators The active isolators in the system are displayed as device addresses in the fields L1 and L2 for 41CPE112 l...

Страница 51: ...eak The loop is broken Loop Short Short circuit detected in the loop New Loop Devices Found New loop devices are found in system configuration Loop 1 or Loop 2 Loop Zero Address There is a device with...

Страница 52: ...or Active Relay Activated relay output of the panel After the message is displayed also the number of the activated relay 1 4 Loop Device Input Active Activated input of a loop device After the messag...

Страница 53: ...41CPE112 Addressable Fire Alarm Panel Installation and Programming Manual 53 APPENDIX C Initial power up of the system...

Страница 54: ...41CPE112 Addressable Fire Alarm Panel Installation and Programming Manual 54 APPENDIX D Two steps of alarming Algorithm...

Страница 55: ...tructure of the programming menus The presented tree structure describes the full access to the programming menus from level 3 Installer From access level 2 Maintenance some of the programming menus a...

Страница 56: ...41CPE112 Addressable Fire Alarm Panel Installation and Programming Manual 56 Tree structure of the menus continue...

Страница 57: ...Comelit Group S p A Via Don Arrigoni 5 24020 Rovetta BG Italy www comelitgroup com 41CPE112 EN...

Отзывы: