41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
32
•
Button ON/ OFF LED BLINK
– Using this button the installer can enable or disable the LED indication
showing the communication between the panel and the respective device. When setting
ON
state, the LED of
the device starts blinking at every 10 seconds in normal operation mode.
Note: Devices 41IOM010, 41SAI000 and 41SAB100 have no LED indication for showing the communication with the
panel.
In the setup menu of every device is introduced a
system ID field
with a unique 10-digit number – the ID number of
the device for identification in the system configuration.
Use the functional digit buttons to enter the respective submenus according the type of the selected device.
41RFU100 / 41RFU000 – Optical-smoke detector with isolator
Use the functional buttons to set the following specialized parameters:
(1) SENSITIV.
– Press the button to enter the submenu for setting
the sensitivity level of the smoke chamber for DAY and NIGHT alarm
mode.
Use the functional buttons (2) DAY and (3) NIGHT to select the
sensitivity level: Normal/ Middle/ Low/ High. All set sensitivity levels
are confirmed with ENTER button.
(3) TEST
– Press the button to enter in a new screen for checking of
the following current parameters:
-
Smoke
: Shows in percent the current level of smoke in the
detector’s smoke chamber.
-
Pollution
: Shows in percent the current level of pollution in the
detector’s smoke chamber.
The exit to the main screen is with pressing the CANCEL button.
41RCS100 / 41RCS000 – Heat Detector with isolator
Use the functional buttons to set the following specialized parameters:
(1) CLASS
–
Press the button to enter the submenu for setting the
class for DAY and NIGHT alarm mode. Use the functional buttons (2)
and (3) to select the class: A1R/ A2S/ BS. The selected class is
confirmed with ENTER button.
(3) TEST -
Press the button to enter in a new screen for checking of
the following current parameters:
-
T fire
– Shows the operating temperature of the detector, in
degrees centigrade.
-
Т
– Shows the current temperature in the room, in degrees
centigrade. The selected class is confirmed with ENTER button.