41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
35
Attention:
It is possible to connect different type of sounders to the loop at the same time, but the total
consumption of the sounders in the loop must be up to 300mA!
Note:
The automatic detectors mounted to bases 41SCB100 are assigned at separate addresses in the control panel!
41SAB100 – Base with sounder
Use the functional buttons to set the following specialized parameters:
(1) SND LEVEL –
Every pressing of the button alternatively changes the sound level between HIGH/ LOW – as this
depends on the number of the connected sounders to the loop:
-
HIGH
– Set in those cases when
the number of the connected sounders* to the loop is up to 30.
-
LOW
– Set in those cases when
the number of the connected sounders* to the loop is up to 100.
(4) ON/ OFF TURN –
Press to switch on/ off the sound of the sounder when checking for double addresses or finding
the place of installation.
Attention:
It is possible to connect
different type of sounders to the loop at the same time, but the total
consumption of the sounders in the loop must be up to 300mA!
Note:
The automatic detectors mounted to bases 41SAB100 are assigned at separate addresses in the control panel!
To calculate the total consumption of the sounders in the loop and to define the proper sound level, you can use the
Table a below, as fill in the number of the used sounders according their type.
Table 1 for calculation of the total consumption of the sounders in the loop with defined sound level and set
ALARM
and/or EVACUATE TONE type 27
(see item 7.6.6 Sounders Mode):
Sounder
Number
HIGH
Sound Level
LOW
Sound Level
Total consumption, mA
(HIGH + LOW)
41SAI000
____ x 16,5mA
____ x 5mA
41SCI000
____ x 22mA
____ x 12mA
41SAB100
____ x 10mA
____ x 3mA
41SCB100
____ x 10mA
____ x 3mA
Consumption of the sounders in the loop:
Table 2 for calculation of the total consumption of the sounders in the loop with defined sound level and set
ALARM
and/or EVACUATE TONE other type sound
(see item 7.6.6 Sounders Mode):
Sounder
Number
HIGH
Sound Level
LOW
Sound Level
Total consumption, mA
(HIGH + LOW)
41SAI000
____ x 10mA
____ x 4mA
41SCI000
___ x 16,5mA
____ x 11mA
41SAB100
____ x 10mA
____ x 3mA
41SCB100
____ x 10mA
____ x 3mA
Consumption of the sounders in the loop: