41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
33
The exit to the main screen is with pressing the CANCEL button.
41RML100 / 41RML000 – Combined optical-smoke and heat detector with isolator
Use the functional buttons to set the following specialized parameters:
(1) SENSITIV. –
Press the button to access the following additional
setting menus:
(1) – Enabling/ Disabling the operation of the thermal part of the
detector. Every pressing of the button changes alternatively the
parameter.
(2) – Setting the sensitivity level in DAY operation mode: Normal/
Middle/ Low/ High. Press the button until reaching the desired
sensitivity level.
(3) - Setting the sensitivity level in NIGHT operation mode: Normal/
Middle/ Low/ High. Press the button until reaching the desired
sensitivity level.
(4) - Enabling/ Disabling the operation of the smoke part of the
detector. Every pressing of the button changes alternatively the parameter.
(3) TEST –
Press the button to enter in a new screen for checking of the following current parameters:
-
Smoke
: Shows in percent the current level of smoke in the detector’s smoke chamber.
-
Pollution
: Shows in percent the current level of pollution in the detector’s smoke chamber.
-
T fire
: Shows the operating temperature of the detector, in degrees centigrade.
-
Т
: Shows the current temperature in the room, in degrees centigrade. The selected class is confirmed with ENTER
button.
The class for 41RML100 is fixed to A1R and could not be changed.
The exit to the main screen is with pressing the CANCEL button.
41PAM000 – Manual call point for indoor mounting
41PAE020 – Manual call point for outdoor mounting IP67
Use the functional buttons to set the following specialized parameters:
(3) EVENT EVACUATION/ ALARM –
Every pressing of the button alternatively changes the type of the event
generated with activation of the manual call point:
-
Event EVACUATION
– The sounders will be activated immediately, as the set time delays Т1 and Т2 are
ignored.
-
Event ALARM
– The set time delays Т1 and Т2 are active and the manual call point operated as an
automatic detector.