41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
48
-
ON –
Set this time interval from 1 to 600 seconds*. During evacuation mode the sounders will operate with
the setting of (4) MORE button described above – for example when SND/FLASH option is set the sounders will
sounding and flashing at the same time (for the models available).
-
OFF -
Set this time interval from 1 to 600 seconds*. During evacuation mode the sounders will operate only in
FLASH mode (for the models available).
* Use the up and down arrow buttons to set the parameter value; use the left and right arrow buttons to switch between
the two parameters.
ATTENTION: The EVAC. CYCLE function is active only when the ON and OFF times are set different from 0.
If
one or both times are set to 0 the function is inactive.
For example: The MODE is set to SND/FLASH and the EVAC. CYCLE TIMES are set ON: 030 sec and OFF: 040 sec.
When Evacuation is in process on the protected site the operation of the system according the EVACUATION
SETTINGS will be the following: The sounders will sound (Evacuation tone) and flash for 30 seconds and then will only
flash for 40 seconds. The cycle will repeat until resetting of the system or pressing the Silence Alarm button.
(4) ZONAL CHANGE
– Press to change the sounders operation mode.
•
Common
- All sounders will be activated with no sense of zone to which they are connected.
•
Zonal
- Only the sounder of the zones with alarm condition will be activated.
7.6.7 Company Logo
Enter company name and site description using the arrow buttons as described in APPENDIX B. The description can
be entered on 2 rows with up to 40 symbols (including spaces) each. To enter symbols and letters use the buttons with
up and down arrows. The cursor is moved with the left and right arrow buttons. After entering the full system name and
information for the site, press “ENTER” button to save it. See also APPENDIX B.
7.7. Save Configuration Menu
Attention: Saving the system configuration is available only from access level 3!
In this menu the installer performs saving of the new found devices in the system configuration. The panel will ask for
confirmation of the action. The screen displays.
Use the functional buttons to confirm or reject the save configuration.
You can also escape from this menu with ‘CANCEL’ button.
7.8. Restore Defaults Menu
Attention: The restore defaults menu is available only from access level 3!
In this menu the installer performs reset to default settings of the system configuration. The panel will ask for
confirmation of the action. The screen displays.
Use the functional buttons to confirm or reject the restore defaults
settings. You can also escape from this menu with ‘CANCEL’ button.