41CPE112 Addressable Fire Alarm Panel – Installation and Programming Manual
9
PROTECTION CONFIRMED
(yellow)
EXTINGUISHING STARTED CONFIRMATION
. Lights on permanently in
activation of the specialized “In PC” input – see the description on page 12.
PROTECTION PANEL FAULT
(yellow)
EXTINGUISHING SYSTEM FAULT
. Lights on permanently in activation of the
specialized “In FP” input – see the description on page 12.
POWER ON
(green)
MAIN POWER SUPPLY ON
. Lights on permanently in presence of 230V main
power supply.
SILENCE ALARM
(yellow)
THE SOUNDERS ARE SILENCED
. Lights on permanently when the sounders
are silenced (the LED is situated next to the button).
2 – Description of the zone LED indication:
LED
Indication/ Description
Zone indicators (red)
1 - 16
FIRE IN A ZONE
. Lights on permanently in case of fire alarm in zones 1-16.
Blinking when zones 1-16 are in test mode.
Note: For zones from 17 to 48 there is no LED indication.
3 – Description of the LCD-module
The 41CPE112 fire alarm addressable panel is equipped with letter-digit LCD-module (4 rows x 40 symbols). The user
can enter device and zone names using the navigation and control buttons. The display has an adjustable backlight
with 20 levels of intensity.
4 – Description of the functional digit buttons:
Button
Description
Functional digit buttons
1 - 4
The buttons are active at access levels 2 and 3, and have the following
meaning:
- Introducing of access codes.
- Functional submenu entry.
- Changing of value or parameter status.
5 – Description of control and navigation buttons:
Button
Action
Description
Silence Buzzer
The button is active at access levels 1, 2 and 3. The button functionality is
deactivation of the internal buzzer.
Silence
Sounders
The button is active at access levels 2 and 3. The button functionality is
deactivation of the sounders in case of fire alarm event. After pressing the button
the LED next to it is lighting in yellow.
Reset
The button is active at access levels 2 and 3. The button functionality is resetting
the panel without switching off the main power supply.
Evacuation
The button is active at access levels 1*, 2 and 3. The button immediately
activates the sounders – the sounder delay is ignored if present.
*
In case of fire alarm event in a zone and set sounder delay.
Buzzer and LED
general test
The button will activate all LEDs on the front panel – for events and zones, as
and the internal buzzer. The next pressing of the button deactivates the test.
ENTER
(Confirmation)
The button is active at access levels 1, 2 and 3. Use the button to confirm the
entered values and parameters; in the devices and zones menus use the button
to enter in a submenu for name and status changing.
CANCEL
(Rejection)
The button is active at access levels 1, 2 and 3. Use the button to reject the
entered values and parameters; one step back to the previous menu.
Navigation
buttons
The button is active at access levels 2 and 3. Use the arrows to scroll over the
menus; in the programming menus the buttons has a specific function for
changing values and switching between the editable fields.