RS-232: To use the monitors with RS-232, activate the RS-232 interface on the VC-1803/04.
Select the port under "Port settings."
•
The RS-232 interface is activated in the web browser. In the System configuration menu under
"com port termination," select COM2 (port 2) and save with "Apply."
•
Check to ensure the wiring of the connected devices is correct.
•
If communication is not established, check the port under "Port settings."
•
Start the search process of the connected monitoring modules with "Start search."
•
After the search function has ended with "Start search," all VC-18xx monitors present in the
network are displayed.
•
Select the required device and continue the process with "Next."
•
To save the complete settings definitively, the VC-1803/04 must be booted again (Reboot).
•
The status LED flashes Green during the restart.
•
RS-485: Connection of the RS-485 chain to VC-1803/04 only via the COM1 screw terminals (port
1).
The VIBROCONTROL 18x0 is now connected by way of the VC-1803/04 communication module.