© Brüel & Kjær Vibro
● C106834.002 / V06 ●
Page 51 of 110
Technical alterations reserved!
Brüel & Kjær Vibro
│
Instruction VC-1800 Series
Vibrocontrol 1870 -
Vibration Measurement and Axial Position
EN
UNRESTRICTED DOCUMENT
Response to overload and over range detection
The graphic below describes the behavior of the monitoring device in response to over range and
overload situations:
Response to over range detection
When the relative shaft vibration (dynamic AC value) is in over range:
•
the corresponding analog output shows 20.5 mA.
When the static sensor position (DC-GAP) is in over range:
•
The corresponding analog output shows either 3.8 mA (below
– sensor moving towards the shaft)
or
•
The corresponding analog output shows 20.5 mA (above
– sensor moving away from the shaft)
- See also the blue graphic above.