In the example below output type "Relay" is selected. It can be changed to Analog Output.
If all outputs (1-4) are defined as analog outputs, the OK relay can be used as a collective relay for all
Danger alarms (Setup Monitor: Safety Monitor (ISO 13849-1).
Please note that all configurable outputs refer to common ground (
GND
). Outputs selected to
be a current source or voltage source will have an output value that can be directly measured
between the respective output terminal and GND.
Please be aware that each of the four outputs can have only one function attached to it. For
example, if all four outputs are selected to be 4-20 mA current outputs, there will be NO relays
available.
Exception: The Protection System feature has been enabled (see section 6.14), which will
cause ALL Danger alarms to trigger the protection system (= system error relay). The
extension module VC-1801 provides 12 additional relays.