Type
Available message types are EVAC, Chime or Business. The Type can be set when adding
messages.
Duration
The duration of the uploaded message, given in format “minutes:seconds”.
Level
Indicates the level of the message. Level ranges from -80 dB to +18 dB. Default level is 0.0 dB.
Use the corresponding spin control to edit the level. The level can be edited in offline or online
mode.
Info
The memory usage is indicated for all MM-2 modules.
ADD
Press the ADD button to upload a new message. A file selection dialog appears (see screenshot
below) that allows selecting a message in WAV file format (mono, 48 kHz). You have to assign a
description and a message type (EVAC; Chime or Business) to the message before uploading. If
there are two MM-2 modules available, the location for the message has to be selected.
HINT: A selection of standard evacuation messages in different languages is available in the
Download area at www.dynacord.com
DELETE
Press the DELETE button to delete the message selected in the message list.
REPLACE
Press the REPLACE button to replace the message selected in the message list, the message
type and location can not be changed. In online mode only business messages can be replaced.
ERROR STATES
The current condition of each type of error gets indicated. Green means no error, red indicates
that an error has been detected.
At the occurrence of a type of error for which the checkbox DETECT is ticked, the COLLECTED
ERROR flag is set at the same time. Additionally the FAULT-LED on the front panel of the DPM
lights, the FAULT relay opens and a signal sounds.
MODULE
Hardware or configuration error in the MM-2 module.
MESSAGE
STORAGE
Error during message storage.
PLAYBACK
MEMORY
Error in the playback memory.
WATCHDOG
Watchdog error of the DPM. This error type is logged conforming to standards.
TEMPERATURE
Temperature of module is too high.
COLLECTED
ERROR
The FAULT-LED on the front panel of the DPM 8016 lights at the occurrence of this type of error.
FALLBACK
SIGNALS
Fallback Evac
Select the default evacuation signal to use if no message is uploaded to the MM-2 module. This
settings is valid for all DPM 8016 in the PROMATRIX system.
Fallback Pre-/
Chime
Select the default chime or pre-chime signal to use if no chime is uploaded to the MM-2 module.
This settings is valid for all DPM 8016 in the PROMATRIX system.
IRIS-Net
PROMATRIX 8000 | en 734
Bosch Security Systems B.V.
User Manual
2017.05 | 3.20 | F.01U.119.956
Содержание IRIS-Net
Страница 1: ...IRIS Net en User Manual ...
Страница 2: ......
Страница 146: ...IRIS Net REMOTE AMPLIFIER en 146 Bosch Security Systems B V User Manual 2017 05 3 20 F 01U 119 956 ...
Страница 148: ...IRIS Net REMOTE AMPLIFIER en 148 Bosch Security Systems B V User Manual 2017 05 3 20 F 01U 119 956 ...
Страница 151: ...IRIS Net REMOTE AMPLIFIER en 151 Bosch Security Systems B V User Manual 2017 05 3 20 F 01U 119 956 ...
Страница 153: ...Layer 5 Control Page IRIS Net REMOTE AMPLIFIER en 153 Bosch Security Systems B V User Manual 2017 05 3 20 F 01U 119 956 ...
Страница 648: ...IRIS Net DIGITAL SOUND PROCESSOR en 648 Bosch Security Systems B V User Manual 2017 05 3 20 F 01U 119 956 ...
Страница 693: ...IRIS Net DIGITAL SOUND PROCESSOR en 693 Bosch Security Systems B V User Manual 2017 05 3 20 F 01U 119 956 ...
Страница 992: ......
Страница 993: ......