D9412GV2/D7412GV2 |
Program Entry Guide | 7.0
RADXAXS
EN
| 135
Bosch Security Systems | 5/05 | F001U003636B
7.0 RADXAXS
7.1
Door Profile
This programming category is used to:
•
Assign an area that also activates the D9210B
•
Assign a point to the door
•
Program the door state to change the time when
the arm state changes
•
Allow for the Strike relay to activate upon a fire
alarm
Door #
Default:
20 sec
Selection:
1 sec to 8 sec
Enter the number of the door you are programming.
The D9412GV2 supports up to eight
doors. The D7412GV2 supports two
doors.
D# Entry Area #
Default:
Blank
Selection:
Blank, 1 to 8
1 to 8
The area assigned to the door
controller to which the reader allows
access.
Blank
Door controller does not function.
Assign an area to the door controller. This entry allows
the D9210B to be polled, activating communication to
the control panel. This is also the area a user exits
when initiating an REX.
All SDI devices, regardless of area
assigned, report to Area 1, Account 1 by
default upon SDI failure. If a D9210B
becomes disconnected, an SDI Fail ##
and a Missing Point ### Event is created.
9210 NOT READY
appears at this keypad
when you press the [ENTER] key if the
D9210B is not programmed with a
D#
Entry Area
.
D#CC#Scope
Default:
Blank
Selection:
Blank, 1 to 8
1 to 8
Determines disarming rights. The
user’s access level and the
CC #
Scope
determines which areas are
disarmed.
Blank
Only the area assigned to the
D#
Entry Area
disarms this door.
Enter the keypad number (CC#) which determines the
scope of the user ID’s disarming rights. Areas disarm
on the basis of this keypad’s scope and the authority
level of the user.
D# Custom Function
Default:
0 (Disabled)
Selection:
0, 128-143
0
Custom function disabled.
128-143
The custom function number that
executes upon a valid ID, given the
appropriate user access level and area
arm state.
You can program a custom function to run at the
keypad programmed for
CC# Scope.
This custom
function activates only for users with an
L## Function
Level?
Assignment (refer to
2.11 User Interface
on
page
54
) in which a valid ID can execute a custom
function during the armed or disarmed state. The user
number to which the token is assigned must have an
assigned pass code.
If
D# Disarm On Open
is set to
Yes
for the same
door, and
L## Function Level?
is set to D or C, the
custom function executes when the door is physically
opened.
A user’s access level and the armed state
of the area determine whether the custom
function activates. This access level is
programmed in the
L## Function Level?
prompt. Refer to
2.11 User Interface
on
page 54.
Table 42
on page 136 shows how this programming
affects custom function activation.
Содержание D7412GV2
Страница 1: ...EN Program Entry Guide Control Panels D9412GV2 D7412GV2 ...
Страница 76: ...D9412GV2 D7412GV2 Program Entry Guide 2 0 GV2MAIN EN 76 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 98: ...D9412GV2 D7412GV2 Program Entry Guide 4 0 RADXPNTS EN 98 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 134: ...D9412GV2 D7412GV2 Program Entry Guide 6 0 GV2AUX EN 134 Bosch Security Systems 5 05 F001U003636B Notes ...