D9412GV2/D7412GV2 |
Program Entry Guide | 4.0
RADXPNTS
EN
| 83
Bosch Security Systems | 5/05 | F001U003636B
P ## Type
Description
Keyswitch Maintained:
Program
P## Pt Response
as 1. Do not connect initiating devices to a
Keyswitch point.
Normal:
The area is disarmed.
Short:
When this point changes from normal to open, the area arms.
Open:
A short is a trouble when the area is disarmed. A short is an alarm when the
area is armed. When this point changes from shorted to normal or open, it
restores.
Program Point Response as 2, the point responds as follows:
Normal:
When this point changes from open to normal, the area arms.
Open:
The area is disarmed.
Short:
A short is a trouble when the area is disarmed. A short is an alarm when the
area is armed. When this point changes from shorted to normal or open, it
restores.
4*
Trouble and Restoral Reports are not sent if
Local While Disarmed
is
Yes
.
Alarm and Restoral Reports are not sent if
Local While Armed
is
Yes
.
Keyswitch Momentary:
Used for area arming and disarming.
Point Response
must be
programmed 1. Do not connect initiating devices to a Keyswitch point.
N
→
S
→
N:
When this point momentarily changes from normal to shorted to normal, it
toggles the armed state of the area.
Open:
An open is a trouble while the point is disarmed. An open is an alarm while the
point is armed.
When this point changes from open to normal, it restores.
5*
Trouble and Restoral Reports are not sent if
Local Disarmed
is
Yes
.
Open/Close Point:
Used for point arming and disarming.
Point Response
must be
programmed 1. Local bells are silenced through the keypad.
Normal:
The point is armed and sends a Point Closing Report. A Point Closing Report
is not sent if Local Armed is
Yes
.
Open:
An open is an alarm when the point is armed. An open is a trouble when the
point is disarmed. Alarm and Restoral Reports are not sent if
Local Disarmed
is
Yes
.
6*
Short:
The point is disarmed and sends a Point Opening Report. A Point Opening
Report is not sent if
Local Armed
is
Yes
.
*
Keyswitch Points: Special rules apply to points used for Keyswitch functions.
These special point types do not respond
the same way to the point response entry as Point Types 1, 2, and 3. Responses for Keyswitch point types are described in
Section 4.2 Point Responses
on page 85.
.
Содержание D7412GV2
Страница 1: ...EN Program Entry Guide Control Panels D9412GV2 D7412GV2 ...
Страница 76: ...D9412GV2 D7412GV2 Program Entry Guide 2 0 GV2MAIN EN 76 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 98: ...D9412GV2 D7412GV2 Program Entry Guide 4 0 RADXPNTS EN 98 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 134: ...D9412GV2 D7412GV2 Program Entry Guide 6 0 GV2AUX EN 134 Bosch Security Systems 5 05 F001U003636B Notes ...