D9412GV2/D7412GV2 |
Program Entry Guide | 6.0
GV2AUX
EN
| 129
Bosch Security Systems | 5/05 | F001U003636B
Example of Retry Count:
An acknowledgment of the heartbeat was not received
within 10 seconds. The control panel sends the
Heartbeat Event after the first 10-sec ack wait period
expires. If the central station does not acknowledge
this Heartbeat Event, the control panel declares this
path as failed (and generates the Comm Fail ##
Event). The control panel continues to re-send the
Heartbeat Event every 10 sec until it receives an
acknowledgment.
When the control panel receives acknowledgment
from the central station, the control panel returns to
the normal Poll Rate (which, in this example, is 120
seconds).
If more than one SDI Path is used, the control panel
handles them on a successive basis. For example, if
acknowledgment from SDI Path 1 is not received
within 10 seconds (using the previous example), the
control panel moves to SDI Path 2 to send its
Heartbeat Event (and subsequently waits for the ack)
before returning to SDI Path 1 to re-send its heartbeat.
If Heartbeat Events are enabled to send by
an SDI path, and the
Path # Ack Wait
time
is exceeded, a
Comm Fail ##
event
occurs. When this condition occurs, all
events routed to this path go immediately
to the backup path.
Entries are made in one-second increments.
Although RPS and the D5200 allow
Path
# Poll Rate
values of 1 to 4, the control
panel interprets these entries as an entry of
5.
5 minutes = 300 seconds
1 hour = 3600 seconds
12 hours = 43,200 seconds
18 hours = 64,800 seconds
Path # Ack Wait
Default:
13
Selection:
0, 5 seconds to 65535 seconds
0
The control panel does not look for
any acknowledgment from the central
station.
5 to 65535
The control panel waits this amount
of time to receive an
acknowledgment from the central
station.
Determines how long the control panel waits for an
acknowledgment from the central station after a
Heartbeat Event (poll) or an actual event was
transmitted. This prompt is applicable only to SDI
transmitted events. Entries are made in one-second
increments.
Although RPS and the D5200 allow
Path
# Ack Wai
t values of 1 to 4, the control
panel interprets these entries as an entry of
5.
The value entered for
Path # Ack Wait
Tone
must not equal the time out entry
made in the RPS Account (refer to the RPS
Operation Manual
, version 3.9 or higher).
Instead, offset these values by 2 or 3. For
example, if your Path # Ack Wait time = 15,
program your Time Out value as 17 in the
RPS account.
Path # Retry Count
Default:
5
Selection:
0 to 255
0
COMM FAIL RG# SDI ### Events
are not generated.
1 to 255
COMM FAIL RG# SDI ### Events
are generated after resending
Heatbeat Event the number of times
for a given SDI path.
Determines how many times the control panel resends
the Heartbeat Event before declaring a path failure
and generating a COMM FAIL RG# SDI ### (RG #
= 1 to 4, SDI ### = 88 for Path 1, 89 for Path 2, 90
for Path 3, 91 for Path 4) Event.
Содержание D7412GV2
Страница 1: ...EN Program Entry Guide Control Panels D9412GV2 D7412GV2 ...
Страница 76: ...D9412GV2 D7412GV2 Program Entry Guide 2 0 GV2MAIN EN 76 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 98: ...D9412GV2 D7412GV2 Program Entry Guide 4 0 RADXPNTS EN 98 Bosch Security Systems 5 05 F001U003636B Notes ...
Страница 134: ...D9412GV2 D7412GV2 Program Entry Guide 6 0 GV2AUX EN 134 Bosch Security Systems 5 05 F001U003636B Notes ...